叙述了作者所领导的课题组在1956—1963年间对北京地区多层民用建筑以及在1979—1983年间对北京地区高层民用建筑的供暖热负荷研究过程、研究目的和取得的成果。鉴于1955年前由于负荷计算不符合实际导致各朝向房间温度不均的现实问题,采用观测手段对供暖建筑进行多次实地测试,并经过对测试数据的认真分析总结,得到了供暖建筑北向修正率为零,其他朝向得益于太阳辐射热,其修正率为负值的结果;针对高层建筑冬季存在的冷风渗透问题,通过对4栋建筑各连续5天的实测,分析、计算得到了居住建筑热压系数0.2、公共建筑热压系数0.5的结论。几十年来的设计实践证明,上述研究成果是正确和可靠的。
Describes the research process, research purposes and achievements of the research group led by the author in 1956-1963 on the multi-storey civil buildings in Beijing and the heating heat load on the high-rise civil buildings in Beijing during 1979-1983. In view of the fact that the load calculation did not accord with the practical problems that caused the uneven temperature in all rooms before 1955, many real-time tests were conducted on the heating buildings by means of observation. After careful analysis and summarization of the test data, the North Building Correction Rate Is zero, the other is due to solar radiation heat, the correction rate is a negative result; for high-rise buildings in winter there is the problem of cold infiltration, through the four buildings of five consecutive days of actual measurement, analysis, calculated residential buildings Hot pressing coefficient of 0.2, hot pressing coefficient of public buildings 0.5 conclusion. Decades of design practice has proved that the above research results are correct and reliable.