A new air exchange rate (AER) monitoring method using continuous CO2 sensors was developed and validated through both laboratory experiments and field studies.Controlled laboratory simulation tests were conducted in a 1-m3 environmental chamber at different AERs (0.1-10.0 hr-1).AERs were determined using the decay method based on box model assumptions.Field tests were conducted in classrooms,dormitories,meeting rooms and apartments during 2-5 weekdays using CO2 sensors coupled with data loggers.Indoor temperature,relative humidity (RH),and CO2 concentrations were continuously monitored while outdoor parameters combined with on-site climate conditions were recorded.Statistical results indicated that good laboratory performance was achieved:duplicate precision was within 10%,and the measured AERs were 90%-120% of the real AERs.Average AERs were 1.22,1.37,1.10,1.91 and 0.73 hr-1 in dormitories,air-conditioned classrooms,classrooms with an air circulation cooling system,reading rooms,and meeting rooms,respectively.In an elderly particulate matter exposure study,all the homes had AER values ranging from 0.29 to 3.46 hr-1 in fall,and 0.12 to 1.39 hr-1 in winter with a median AER of 1.15.