地埋管壁厚对地源热泵运行的影响

来源 :建筑节能 | 被引量 : 0次 | 上传用户:pt315311
下载到本地 , 更方便阅读
声明 : 本文档内容版权归属内容提供方 , 如果您对本文有版权争议 , 可与客服联系进行内容授权或下架
论文部分内容阅读
对上海地区地源热泵单U型地埋管换热器的运行进行实验研究,建立地埋管传热模型,且对实验数据进行理论计算并验证,以探究地埋管的壁厚对地源热泵运行效果的影响。研究结果表明:在上海地区,常用的40 mm聚乙烯(PE80)地埋管壁厚每增加0.5 mm,埋管内进出口平均水温上升约0.18℃,地源热泵机组的COP下降约0.5%。这将为上海地区地埋管换热器的设计提供一定的参考作用。 In this paper, an experiment was conducted on the operation of a U-type ground tube heat exchanger in Shanghai area. The heat transfer model was established and the theoretical calculation and verification of the experimental data were carried out to investigate the effect of buried pipe wall thickness on ground source Effect of heat pump operation. The results show that the average water temperature at entrance and exit of buried PE pipe increases about 0.18 ℃ for each 0.5 mm increase of wall thickness of commonly used 40 mm polyethylene (PE80) buried pipe in Shanghai, and the COP of ground source heat pump unit drops about 0.5%. This will provide a reference for the design of buried pipe heat exchangers in Shanghai.
其他文献
随着经济的飞速发展。科学水平的快速提升,我国房地产市场竞争越发激烈,在市场经济下,工程管理模式的选择是否合理、适当。将直接关系到建筑工程项目的成败。本文就房屋建筑工程
道路石油沥青含蜡量试验表明,沥青的含蜡量将直接影响到沥青材料的路用性能。文中重点分析影响沥青含蜡量的因素。通过技术检测对沥青含蜡量加强控制。沥青含蜡量对沥青的影
在资深的现代文学研究者中,支克坚先生无疑是写得少而精的一位.他的半生的学术心血都尽萃于这本<中国现代文艺思潮论>(1999年12月,兰州大学出版社出版)中.不待说,在新旧世纪
通过砖砌体结构房屋底层墙下端支承点取室外地面下0.5m和基础顶、地面处、是否考虑室外地面嵌固高度.4个模型代表墙段受压、受剪、高厚比计算结果对比分析和震害总结,提出无地下
期刊
各省、自治区住房和城乡建设厅,直辖市建委(建交委),北京市规委,新疆生产建设兵团建设局:为推动建立统一开放、公平竞争的建筑市场秩序,促进建筑企业持续健康发展,现就进一步做好建筑
载体桩作为一种新桩型,其施工工艺和施工设备已较成熟,且在工程中得到很好的推广。本文主要介绍载体桩设计计算过程中,如何确定载体下深度修正后的地基承载力特征值fa,并依据
结合麻柳湾至凯里高速公路施工图测设的工程实践,分析岩溶对公路的危害,并针对岩溶不同的发育特点提出相应的工程处理措施.
1、陈轸秘书长:在理事会和常务理事会闭会期间,按分工主持分会的日常工作;贯彻执行会长工作会议决定;主持秘书处的工作,分管技术专家委员会和财务与资产管理委员会工作。
(四)"求全责备":对支克坚先生反思的再反思及其他1.反思思维的矛盾性和历史研究的真问题知识分子在新时期事实上迎来了一个再启蒙的因而也更为注重个性和自由的时代,而随着20