摘要:随着电网结构的愈加复杂,对系统的安全稳定性要求也进一步提高。因此,为了确保变电站的安全运行,设置了具有“五防”功能的闭锁装置,能有效防止电气误操作装置的管理,减少电气误操作事故的发生,进一步保障电网的安全运行。本文主要探讨了新型微机防误闭锁装置在变电运行中的应用,同时提出了切合运行实际、行之有效的管理方法。
关键词:微机防误闭锁装置;误操作;五防
Abstract: Along with the network structure more complex, but also further improve the requirements on the security and stability of the system. Therefore, in order to ensure the safe operation of the substation, the locking device with "five prevention" function, can effectively prevent the device electrical disoperation management, reduce the occurrence of electrical disoperation accident, to guarantee the safe operation of power grid. This paper mainly discusses the application of a new type of microcomputer anti disoperation locking device in substation operation, and puts forward the management method with practical operation, effective.Keywords: Anti misoperation lockout device microcomputer; operation; five case
中图分类号:F407.6文献标识码A 文章编号
随着计算机技术的不断发展和应用,微机型“五防”技术将更大程度地应用于变电站防误功能中。从目前的运行情况来看,从安全角度考虑,在大力推广应用微机“五防”系统的同时,应适度保留间隔的电气闭锁回路,或将“五防”系统的接点引入到操作回路中,将是比较有效的防误闭锁措施。为了能有效地实现五防功能,有效地避免操作事故的发生,必须在电气设备上设置闭锁装置或装设微机五防系统,而当前的微机防误闭锁已成为防止操作事故发生的行之有效的方法。
1、系统组成及其功能的实现
新型微机防误闭锁系统以PC机(控制主机)为核心,由主机(PC机)、大屏幕显示器、电脑钥匙(FKYD)、通讯适配器、五防编码锁及解锁工具组成。
主机中内装图形模拟系统、操作票专家系统、智能语音系统、操作管理系统,电脑钥匙通过通讯适配器与主机相联。经过改造后的五防系统是电站综合自动化系统下的一个子系统,它利用网络技术,通过与监控系统联接,完成监控后台五防功能下的对位、操作和闭锁;通过主机与电脑钥匙通讯和传送程序,对现场编码锁进行开闭操作,从而实现现场五防功能下的对位、操作和闭锁。
2、系统特点及关键技术
该系统具有如下特点:一是采用了先进的图形模拟系统,以大屏幕显示器替代传统模拟屏作为系统的操作界面,配置通讯适配器实现模拟操作、操作票传输、五防闭锁、仿真培训等功能;二是采用数据库结构,系统可维护性好,可自行绘制与修改主接线图,可定义与修改五防闭锁关系程序,扩容方便,可扩展性强;三是配置操作票专家系统,并具有打印、显示、存储、删除操作票和操作权限分级管理等功能;四是通过与监控系统通讯接口,实现了与现场一次设备实时在线自动对位功能;五是配置智能语音系统,提供从模拟预演到现场倒闸操作全程的语音提示,并能以专业五防术语智能化提示错误操作类型。
3、防误装置的要求
防误装置应具备以下基本要求:结构简单、可靠、操作维护方便,尽可能不增加正常操作和事故处理的复杂性;应有专用的解锁工具(钥匙),防误装置应满足所配设备的操作要求,并与所配用设备的操作位置相对应;防误装置应不影响开关、隔离刀闸等设备的主要技术性能(如合闸时间、分闸时间、速度、操作传动方向角度等)。
4、防误闭锁装置的管理
4.1电动刀闸操作箱也应纳入规范化管理,电动按钮及分合闸中间继电器(接触器)应有防误碰措施,对没有电气闭锁的电动刀闸操作后应及时断开操作电源,刀闸操作电源必须有独立的控制开关,且操作电源必须取自电机电源。
4.2 手动操作的接地刀闸以及35kV及以下电压等级的综自柜刀闸、手车开关的操作采用机械闭锁是最有效的防误闭锁,因而应加强此类闭锁设备的投产验收、运行维护工作。
4.3 对操作不到位,即在操作某一机构时中途停下来,未完成整套操作,则防误锁应锁不上。针对不同类型机构的特点,对不同电压等级的隔离开关、接地刀闸以及网门等采取具体措施(加装位置对应装置),增加不同的附件以达到防空行程的目的。
4.4 微机五防系统采用多票操作模式,编写与执行操作票时通常是一份接一份的模式,存在“操作票排队”的问题,影响了停送电操作的时间,限制了并列或交叉的可能性,与实际不相符。针对多操作票模式应从实用性和安全性两方面综合考虑,对一些无关联的操作实行多票操作,消除时间上的“空耗”,提高运行人员的工作效率,解决操作时间影响停送电时间的问题。
4.5 目前采用越来越多的电动隔离,刀闸(含地刀)、电气闭锁应作为开放电机电源的必需条件,它是在微机五防监控系统出现故障后避免误操作的措施,因此完善电气二次回路闭锁的逻辑是防止此类误操作的首要前提。由于电气闭锁的条件较为复杂,又有多种条件可实现同一操作的闭锁,不同的设计人员有不同的理解,电气闭锁的条件受人员水平的限制影响大,因此电气闭锁的条件很不完善,漏洞较多,存在严重的安全隐患(特别是主变三侧的接地刀闸的电气闭锁条件)。因此,建议网公司制定统一的五防闭锁逻辑,统一规范、统一管理。
5、建议采用如下的方案
传统闭锁方法发展起来的一套行之有效的防误闭锁方法,实现起来方便、可靠,但回路复杂,间隔多的大型变电站实行起来耗费大量电缆,且在运行中存在开关辅助接点工作不可靠、户外电磁锁机构易损坏等问题,机械结构复杂,安装要求高,常出现卡滞现象。其防误功能不易增加和修改,不能实现“完全微机五防”功能。
微机防误闭锁系统通过软件将现场大量的二次闭锁回路和操作行为变为电脑中的“五防”闭锁规则库,实现了防误闭锁的数字化,并可以实现以往不能实现或者是很难实现的防误功能,应该说是电气设备防误闭锁技术的最新飞跃。但微机防误闭锁系统的漏洞及其致命的弱点在于“五防”功能以操作逻辑为核心,对于无票操作和误碰(主要是检修人员)及二次绝缘破坏则有可能防不住。通过分析传统电气二次闭锁回路和现代微机防误闭锁系统各自的特点,对于新建和改造的变电站,我们建议采用的“五防”闭锁系统方案如下:
首先,建议在监控的变电站,尤其是现推行的无人值班集控站,均应采用同一厂家的微机防误闭锁系统,便于统一规约与监控,便于维护。
方案一:通过监控系统的逻辑闭锁软件实现全站的防误操作闭锁功能,同时在受控设备的操作回路中串接本间隔的闭锁回路,可以考虑不设计或取消传统闭锁装置,所有防误功能由微机“五防”系统独立完成,并且要求微机防误闭锁系统有“防空程”措施。
方案二:监控系统设置“五防”工作站。远方操作时通过“五防”工作站实现全站的防误操作闭锁功能,就地操作时则由电脑钥匙和锁具来实现,同时在受控设备的操作回路中串接本间隔的闭锁回路。可以考虑部分不设计或部分取消传统闭锁(主要是指接地开关电磁锁和综合闭锁),防误工能由微机防误闭锁系统和间隔闭锁共同完成。要求微机防误闭锁系统有“防空程”措施。
方案三:配置独立专用微机“五防”系统。远方操作时通过“五防”系统实现全站的防误操作闭锁功能,就地操作时则由电脑钥匙和锁具来实现,同时在受控设备的操作回路中串接本间隔的闭锁回路。专用微机“五防”系统与变电站监控系统应共享采集的各种实时数据,不应独立采集。不设计或取消电气二次回路闭锁,但在电动操作的开关或接地开关机构箱的操作电源u回路中加入微机防误闭锁系统的强制接点,防误功能由微机防误闭锁系统独立完成,并要求微机五防系统有“防空程”措施。
6、结语
微机防误闭锁装置是电气闭锁技术上的一次巨大飞跃,也是今后发展的主要方向。要将人和微机防误闭锁装置结合起来,以确保电网安全运行。
参考文献:
[1]中华人民共和国能源部安全环保司,防止电气误操作装置管理规定[M].北京:中国电力出版社,1991:2-4,7-9
[2]中华人民共和国能源部安全环保司,关于防止电力生产重大事故的二十项重点要求[M].北京:中国电力出版社,1992:811,i3.
[3]国家电网公司,防止电气误操作装置管理规定[M].北京:中国电力出版社,20003:5-8,12.
[4]國家电网公司,国家电网公司电力安全工作规程[M]北京:中国电力出版社,20005:5-10.
关键词:微机防误闭锁装置;误操作;五防
Abstract: Along with the network structure more complex, but also further improve the requirements on the security and stability of the system. Therefore, in order to ensure the safe operation of the substation, the locking device with "five prevention" function, can effectively prevent the device electrical disoperation management, reduce the occurrence of electrical disoperation accident, to guarantee the safe operation of power grid. This paper mainly discusses the application of a new type of microcomputer anti disoperation locking device in substation operation, and puts forward the management method with practical operation, effective.Keywords: Anti misoperation lockout device microcomputer; operation; five case
中图分类号:F407.6文献标识码A 文章编号
随着计算机技术的不断发展和应用,微机型“五防”技术将更大程度地应用于变电站防误功能中。从目前的运行情况来看,从安全角度考虑,在大力推广应用微机“五防”系统的同时,应适度保留间隔的电气闭锁回路,或将“五防”系统的接点引入到操作回路中,将是比较有效的防误闭锁措施。为了能有效地实现五防功能,有效地避免操作事故的发生,必须在电气设备上设置闭锁装置或装设微机五防系统,而当前的微机防误闭锁已成为防止操作事故发生的行之有效的方法。
1、系统组成及其功能的实现
新型微机防误闭锁系统以PC机(控制主机)为核心,由主机(PC机)、大屏幕显示器、电脑钥匙(FKYD)、通讯适配器、五防编码锁及解锁工具组成。
主机中内装图形模拟系统、操作票专家系统、智能语音系统、操作管理系统,电脑钥匙通过通讯适配器与主机相联。经过改造后的五防系统是电站综合自动化系统下的一个子系统,它利用网络技术,通过与监控系统联接,完成监控后台五防功能下的对位、操作和闭锁;通过主机与电脑钥匙通讯和传送程序,对现场编码锁进行开闭操作,从而实现现场五防功能下的对位、操作和闭锁。
2、系统特点及关键技术
该系统具有如下特点:一是采用了先进的图形模拟系统,以大屏幕显示器替代传统模拟屏作为系统的操作界面,配置通讯适配器实现模拟操作、操作票传输、五防闭锁、仿真培训等功能;二是采用数据库结构,系统可维护性好,可自行绘制与修改主接线图,可定义与修改五防闭锁关系程序,扩容方便,可扩展性强;三是配置操作票专家系统,并具有打印、显示、存储、删除操作票和操作权限分级管理等功能;四是通过与监控系统通讯接口,实现了与现场一次设备实时在线自动对位功能;五是配置智能语音系统,提供从模拟预演到现场倒闸操作全程的语音提示,并能以专业五防术语智能化提示错误操作类型。
3、防误装置的要求
防误装置应具备以下基本要求:结构简单、可靠、操作维护方便,尽可能不增加正常操作和事故处理的复杂性;应有专用的解锁工具(钥匙),防误装置应满足所配设备的操作要求,并与所配用设备的操作位置相对应;防误装置应不影响开关、隔离刀闸等设备的主要技术性能(如合闸时间、分闸时间、速度、操作传动方向角度等)。
4、防误闭锁装置的管理
4.1电动刀闸操作箱也应纳入规范化管理,电动按钮及分合闸中间继电器(接触器)应有防误碰措施,对没有电气闭锁的电动刀闸操作后应及时断开操作电源,刀闸操作电源必须有独立的控制开关,且操作电源必须取自电机电源。
4.2 手动操作的接地刀闸以及35kV及以下电压等级的综自柜刀闸、手车开关的操作采用机械闭锁是最有效的防误闭锁,因而应加强此类闭锁设备的投产验收、运行维护工作。
4.3 对操作不到位,即在操作某一机构时中途停下来,未完成整套操作,则防误锁应锁不上。针对不同类型机构的特点,对不同电压等级的隔离开关、接地刀闸以及网门等采取具体措施(加装位置对应装置),增加不同的附件以达到防空行程的目的。
4.4 微机五防系统采用多票操作模式,编写与执行操作票时通常是一份接一份的模式,存在“操作票排队”的问题,影响了停送电操作的时间,限制了并列或交叉的可能性,与实际不相符。针对多操作票模式应从实用性和安全性两方面综合考虑,对一些无关联的操作实行多票操作,消除时间上的“空耗”,提高运行人员的工作效率,解决操作时间影响停送电时间的问题。
4.5 目前采用越来越多的电动隔离,刀闸(含地刀)、电气闭锁应作为开放电机电源的必需条件,它是在微机五防监控系统出现故障后避免误操作的措施,因此完善电气二次回路闭锁的逻辑是防止此类误操作的首要前提。由于电气闭锁的条件较为复杂,又有多种条件可实现同一操作的闭锁,不同的设计人员有不同的理解,电气闭锁的条件受人员水平的限制影响大,因此电气闭锁的条件很不完善,漏洞较多,存在严重的安全隐患(特别是主变三侧的接地刀闸的电气闭锁条件)。因此,建议网公司制定统一的五防闭锁逻辑,统一规范、统一管理。
5、建议采用如下的方案
传统闭锁方法发展起来的一套行之有效的防误闭锁方法,实现起来方便、可靠,但回路复杂,间隔多的大型变电站实行起来耗费大量电缆,且在运行中存在开关辅助接点工作不可靠、户外电磁锁机构易损坏等问题,机械结构复杂,安装要求高,常出现卡滞现象。其防误功能不易增加和修改,不能实现“完全微机五防”功能。
微机防误闭锁系统通过软件将现场大量的二次闭锁回路和操作行为变为电脑中的“五防”闭锁规则库,实现了防误闭锁的数字化,并可以实现以往不能实现或者是很难实现的防误功能,应该说是电气设备防误闭锁技术的最新飞跃。但微机防误闭锁系统的漏洞及其致命的弱点在于“五防”功能以操作逻辑为核心,对于无票操作和误碰(主要是检修人员)及二次绝缘破坏则有可能防不住。通过分析传统电气二次闭锁回路和现代微机防误闭锁系统各自的特点,对于新建和改造的变电站,我们建议采用的“五防”闭锁系统方案如下:
首先,建议在监控的变电站,尤其是现推行的无人值班集控站,均应采用同一厂家的微机防误闭锁系统,便于统一规约与监控,便于维护。
方案一:通过监控系统的逻辑闭锁软件实现全站的防误操作闭锁功能,同时在受控设备的操作回路中串接本间隔的闭锁回路,可以考虑不设计或取消传统闭锁装置,所有防误功能由微机“五防”系统独立完成,并且要求微机防误闭锁系统有“防空程”措施。
方案二:监控系统设置“五防”工作站。远方操作时通过“五防”工作站实现全站的防误操作闭锁功能,就地操作时则由电脑钥匙和锁具来实现,同时在受控设备的操作回路中串接本间隔的闭锁回路。可以考虑部分不设计或部分取消传统闭锁(主要是指接地开关电磁锁和综合闭锁),防误工能由微机防误闭锁系统和间隔闭锁共同完成。要求微机防误闭锁系统有“防空程”措施。
方案三:配置独立专用微机“五防”系统。远方操作时通过“五防”系统实现全站的防误操作闭锁功能,就地操作时则由电脑钥匙和锁具来实现,同时在受控设备的操作回路中串接本间隔的闭锁回路。专用微机“五防”系统与变电站监控系统应共享采集的各种实时数据,不应独立采集。不设计或取消电气二次回路闭锁,但在电动操作的开关或接地开关机构箱的操作电源u回路中加入微机防误闭锁系统的强制接点,防误功能由微机防误闭锁系统独立完成,并要求微机五防系统有“防空程”措施。
6、结语
微机防误闭锁装置是电气闭锁技术上的一次巨大飞跃,也是今后发展的主要方向。要将人和微机防误闭锁装置结合起来,以确保电网安全运行。