论文部分内容阅读
以与温湿度独立空调系统相结合的毛细管辐射空调为研究对象,通过实验研究的方法研究了毛细管辐射空调采用高温水系统工况时,不同安装方式、水系统参数、空气设定参数等条件对毛细管空调供冷性能的影响。实验结果表明:裸露安装方式的毛细管辐射供冷能力约为表面与金属板结合的2倍;采用室内空气温度28℃条件比26℃条件下的供冷能力高20%~30%;通过调节流量降低泵耗的方式会使毛细管辐射空调供冷量能力降低。
Taking capillary air-conditioning combined with temperature and humidity independent air-conditioning system as the research object, this paper studied the conditions of different installations, water system parameters and air setting parameters Effect of Capillary Air Conditioning on Cooling Performance. The experimental results show that the radiative cooling capability of the capillary with bare mounting mode is about twice that of the combination of the surface and the metal plate. The indoor air temperature of 28 ℃ is 20% ~ 30% higher than the cooling capacity of 26 ℃. By adjusting the flow rate The way to reduce pump consumption will reduce the capacity of the capillary tube radiating air-conditioning cooling capacity.