湖北省档案馆新馆是一座较为现代化的档案馆建筑。馆房大楼共13层,库房全部为无窗厚墙体建筑,3层以上有环廊,3层以下无环廊有裙房。为了了解库房温湿度状况,保证新馆按期投人使用,我馆从1988年7月开始对新库内外温湿度进行了长期测试。通过测试,我们发现库房温度较为理想,湿度较高,全年无论什么季节,库内相对湿度总是在90%左右。峻工后的库房为何湿度高!我们认为有两种可能:一是库房墙体本身的施工水分未挥发完;二是库外的湿空气向库内的渗透所致。为了找出真正的症结所在,我们对第3、5两层库房进行了密封去湿实验。经过1个月连续实验,在对所获取的数据进行了认真地分析、研究、比较后,发现有两种情况值得注意,一是第3层库房的3台去湿机每天平均出水70斤,第5层库房每天平均出水67斤,按正常情况,在墙体含水量已经基本稳定的条件下,应是越抽越少,但1个月后,每日出水量仍保持初始状态,似乎永远有抽不完的水;第二是3、5两层库房当天去湿后,
Hubei Provincial Archives new museum is a more modern archives building. There are 13 storehouses and all the storerooms are wallless thick wall buildings. There is a ring gallery above the 3rd floor and a podium below the 3rd floor. In order to understand the condition of temperature and humidity in the warehouse and ensure that the new building is put into operation on schedule, our laboratory has conducted long-term tests on the temperature and humidity inside and outside the new warehouse since July 1988. Through the test, we found that the warehouse temperature is ideal, high humidity, no matter what the season throughout the year, the relative humidity in the library is always about 90%. After the completion of the warehouse why the humidity is high! We think there are two possibilities: First, the construction of the warehouse wall itself is not finished evaporation of water; the second is the wet air outside the reservoir infiltration caused by the library. In order to find out the real crux of the problem, we conducted a sealed dehumidification experiment on the fifth and fifth floors of the warehouse. After a month of continuous experiments, the data obtained after careful analysis, research, comparison, found that there are two cases worth noting, first, the third floor warehouse 3 dehumidifiers per day on average 70 pounds of water, The fifth floor of the warehouse an average of 67 pounds of water per day, according to normal circumstances, the water content in the wall has been basically stable conditions, should be more pumping less, but a month later, the daily water volume remains the initial state, it seems forever There are endless pumping of water; the second is 3,5 two-storey warehouse to dehumidify the same day,