我厂位于市内居民集中地,锅炉房与居民住宅仅一墙之隔。锅炉配用的鼓、引风机所产生的噪声不仅影响了操作工人的身体健康,而且使周围居民无法正常休息与睡眠,居民意见很大,曾多次向市有关部门反映。为此,我厂于80年8月对锅炉房进行了噪声现场测试,并提出了治理方案。我厂锅炉房的一台KZG1-3型快装锅炉(1吨/小时),配用6—46#4,1750转/分鼓风机,和Y 4—70#5,2400转/分引风机各一台。经测试,工作机房噪声值为33dBA,而引起机房内噪声值达92dBA,影响到附近居民住房内噪声也竟达59dBA。特别是晚上,这样强的噪声使居民根本无法入睡。
I plant located in the city residents concentrated, boiler room and residential buildings separated by only one wall. Boiler equipped drum, induced draft fan noise not only affects the health of workers, but also to the surrounding residents can not rest and sleep, residents have great opinions, has repeatedly to the relevant departments of the city to reflect. To this end, I plant in August 80 conducted a noise test of the boiler room, and put forward the management plan. A KZG1-3 fast boiler (1 ton / hour) of the boiler room of our factory is equipped with 6-46 # 4,1750 RPM blowers and Y 4-70 # 5,2400 RPM blowers One After testing, the working room noise value is 33dBA, which caused the noise value of the engine room up to 92dBA, affecting the nearby residential buildings as much as 59dBA of noise. Especially at night, such a strong noise makes it impossible for residents to fall asleep at all.