介绍了某电厂500kV GIS设备全电压运行后,盆式绝缘子表面闪络引起的GIS导体对外壳放电的故障。从保护装置动作信息初步确定了故障点区域,经设备绝缘测量确定了故障点具体区域,再经故障点区域设备拆解,查找故障原因是盆式绝缘子闪络。通过设备拆解分析产生闪络的因素是安装时杂质进去该区域,最后从笔者提出针对电厂要检测其余SF6气室,消除可能存在的隐患,安装施工环节厂家人员与监理一同监督施工环节,加强施工质量的防范措施。
The failure of GIS conductor to discharge the case caused by the flashover of the surface of a pot insulator after the full voltage operation of a 500 kV GIS in a power plant is introduced. From the action information of protection device, the fault point area is initially determined. The specific area of the fault point is determined by the equipment insulation measurement, and then the equipment of the fault point area is disassembled to find the cause of the fault flashover of the pot insulator. Through the equipment disassembly analysis flashover factor is the installation of impurities into the area, and finally proposed from the author for the power plant to detect the remaining SF6 gas chamber to eliminate possible hidden dangers, the installation of the construction section of the factory staff and supervision with the construction supervision, strengthening Prevention of construction quality.