对某热电厂75 t/h中温分离器型循环流化床锅炉进行SNCR技术改造,试验结果表明:脱硝率总体可达到35%~65%,并呈现随锅炉负荷增加而降低的趋势;脱硝率随氨氮比(NSR)的增大而升高,但升高趋势越来越缓缓,且当氨氮比大于4.5后氨逃逸值显著增加。锅炉负荷大于45 t/h时,各工况下氨逃逸均能小于8 ppm;在较低负荷时逃逸量较高,选择合适的氨氮比仍可使氨逃逸小于8 ppm并保持大于45%的脱硝率。经过调试,使锅炉各个负荷下NOx排放浓度均低于国家标准规定的100 mg/Nm3,并维持氨逃逸水平不大于8 ppm。实现了国内首次将SNCR脱硝技术应用于中温分离器型循环流化床锅炉。
The SNCR technology retrofit of a 75 t / h medium temperature cyclone-type circulating fluidized bed boiler in a thermal power plant shows that the total denitration rate can reach 35% -65%, and shows a tendency of decreasing as the boiler load increases. The rate of denitrification Ammonia nitrogen ratio (NSR) increases, but the increasing trend is more and more slowly, and ammonia slip ratio increases significantly when ammonia nitrogen ratio is greater than 4.5. When the boiler load is more than 45 t / h, the ammonia slip can be less than 8 ppm under all operating conditions; while at lower load, the escape rate is higher; ammonia slip less than 8 ppm and greater than 45% De-NOx rate. After commissioning, the NOx emission concentration under each load of the boiler is lower than 100 mg / Nm3 as prescribed by the national standard, and the ammonia slip level is maintained at not more than 8 ppm. The first time in China to SNCR denitrification technology used in the temperature separator circulating fluidized bed boiler.