高层建筑消防给水系统管网上常易发生十分棘手的超压问题,特别是消火栓系统和自动喷淋系统合用水泵时这个问题更是严重。这是由于高层建筑消防用水量较大,但在火灾初期消火栓的实际使用数和自动喷水灭火系统的喷头实际开放数要比规范规定的数量少,其实际消防用水量远远小于水泵选定的流量值;消防水泵在试验和检查时,水泵的出水量也较少,此时,管网压力升高,有时超过管网允许压力,容易造成事故,破坏管网的正常工作。为此特在地下室二台消防泵的压水管至消防给水管网分割阀门左、左各加装DN100、水力控制500X新型泄压阀一个,管路直接接至排水坑(泄压管系统),解决了消防给水管网超压时自动泄压排水的大问题,当管网超过安全设定值之压力时,水会自动释放,因而维持管中压力于安全设定值以下,
High-rise building fire water supply systems often have troublesome overpressure problems on the pipe network, especially when the fire hydrant system and the automatic sprinkler system share the use of pumps. This is due to the fact that high-rise buildings have a large amount of fire fighting water, but the actual number of fire hydrants used in the early stages of fires and the actual number of sprinkler heads used in automatic sprinkler systems are smaller than the number prescribed by the regulations. The actual fire water consumption is far less than the pump selection. The value of the flow; fire pump in the test and inspection, the pump output is also less, at this time, the pipe network pressure, sometimes exceeding the pipe network allowable pressure, easily lead to accidents, damage to the normal work of the pipe network. To this end, in the basement two fire pump pressure pipes to the fire water supply pipe network split valve left and right to install DN100, hydraulic control 500X new pressure relief valve, the pipeline directly to the drain pit (pressure relief pipe system), Solved the problem of automatic pressure relief drainage when the fire water supply pipe network overpressure, when the pipe network exceeds the pressure of the safety setting value, the water will be automatically released, thus maintaining the pressure in the pipe below the safety setting value,