毛细管网供冷室内环境对比实验研究

来源 :土木建筑与环境工程 | 被引量 : 0次 | 上传用户:liongliong514
下载到本地 , 更方便阅读
声明 : 本文档内容版权归属内容提供方 , 如果您对本文有版权争议 , 可与客服联系进行内容授权或下架
论文部分内容阅读
  
  4.重庆电讯职业学院,重庆 402247 5.重庆远鉴旅游规划设计有限公司,重庆401120)摘要:对重庆地区毛细管网18℃供水温度下辐射供冷系统进行实验测试,分析了毛细管网顶棚、墙面、地面3种敷设方式室内热工参数。结果表明:毛细管网顶棚、墙面、地面3种敷设方式供冷稳定时,人员活动区的平均温度依次为26.27℃、27.22℃、26.57℃,辐射表面平均温度依次为20.96℃、21.14℃、22.76℃,PMV依次为-0.27、0.32、-0.2,PPD依次为7.06%、7.47%、6.34%。在实验条件下,3种敷设方式供冷时室内温度均能满足≤28℃的要求,PMV、PPD均能满足《民用建筑室内热湿环境评价标准GB/T50785 -2012》I级热舒适评价指标。
  关键词:毛细管网;辐射供冷;敷设位置 PMV和PPD
  中图分类号:TU831    文献标识码:A  文章编号:
  4.Chongqing Telecommunication Polytechnic College,Chongqing 402247,China; 5.Chongqing Yuanjian Tourism Planning & Design Co. Ltd,Chongqing401120,China)Abstract: Tests of capillary radiant cooling system in Chongqing district were taken and thermal parameter were analyzed in conditions of three different capillary laying modes (ceiling, wall and floor) with 18℃ supply water temperature. It concluded that when capillaries were laid on the ceiling, wall and floor respectively, the average temperature of working area was 26.27℃, 27.22℃ and 26.57℃ respectively and the radiation surface temperature was 20.96℃, 21.14℃ and 22.76℃ in turn. By calculation, the PMV of three conditions was-0.27, 0.32 and -0.2 and PPD results were 7.06%, 7.47% and 6.34% respectively. It illustrated that all three laying ways at this experimental conditions could meet the air temperature requirements (no more than 28℃) and PMV, PPD attain thermal environment category I.
  Key words: Capillary;Radiant cooling;Laying way;PMV and PPD
  
  毛細管网作为一种新型空调末端形式,具有不占用室内空间、能与可再生能源结合及室内舒适度更高等优势,受到越来越多的关注。在能源成本越来越高、环境污染与温室效应加剧的大背景下,毛细管网的研究与应用越来越多。
  国外,R.HOSEGGEN[1]等人针对顶棚供冷节能与舒适度进行实验研究,同时利用ESP-r软件进行模拟论证,结果表明:模拟结果与实验数据结果吻合。MIKESKA T[2]等人针对辐射供冷室内舒适性与供水温度关系进行研究,结果表明:当室内温度比供水温度高4 K时,室内温度舒适性较好。MELANIE F[3] 等人针对新型辐射顶棚通过实验实测与模拟进行性能测试,结果表明:新型辐射顶棚性能优于常规辐射顶棚。KEBLAWI A[4]等人针对顶棚供冷辅助新风系统,设计遗传算法控制器,可实现低能耗下满足同样的舒适度。LEE K G[5]等人针对地面辐射与对流空调系统通过实测对比分析,结果表明:辐射空调系统室内垂直温差较小。EUSEBIO Z.E[6]等人针对辐射与对流空调系统通过实验进行对比分析,结果表明:辐射空调系统室内舒适度好。KYU N R[7]等人总结分析了近50年辐射空调系统应用,得出辐射空调系统在节能性、舒适性方面不断改进优化的结论。
  国内,李炅[8]等人针对毛细管网进行模拟研究,分析了毛细管网供冷能力影响因素。朱备[9]等人针对毛细管网辐射供冷表面结露进行研究,明确结合过冷度的运行策略。谢东[10]等人与王赟[11]等人均针对毛细管顶棚辐射供冷进行模拟研究,分析了顶棚辐射供冷时的供冷量。张金明[12]等人针对壁面辐射供冷与对流空调系统进行模拟研究,对比两种空调方式下室内热工参数。刘猛[13]等研究了不同供水温度与室外天气下毛细管网地棚供冷房间温度,供冷量与结露情况。李妍[14]等人分析了影响毛细管网的供冷能力相关曲线图。陈金华[15]等人针对毛细管网地面不同供水温度供暖研究室内参数,确定了供暖的最佳供水温度。陈露[16]等人针对毛细管网顶棚、墙面、地面进行模拟研究,分析了3种敷设方式舒适性。
  通过文献查阅可知,针对顶棚、墙面、地面毛细管网的研究,均为理论计算与软件模拟,或只针对一种敷设方式进行实验研究。文章通过毛细管网顶棚、墙面、地面3种敷设方式实验研究。从室内人员活动区温湿度、壁面温度、室内垂直与水平温度、PMV、PPD等热工参数全面分析3种敷设方式毛细管网供冷的室内舒适性。   
  1实验系统介绍
  1.1实验房间概况
  实验地点为两间相同房间[17]如图1所示,房间410,房间412,每个房间的面积为21m2,尺寸为6m×3.5m×2.7m(长×宽×高),门洞的尺寸0.8m×2.1m(宽×高),外窗的尺寸2700mm×2000mm(宽×高);建筑外墙为实心砖墙(未做保温),厚度为240mm,内墙也为实心砖墙,厚度为200mm。窗户为单层玻璃窗,厚度为6mm,内设厚窗帘。
  
  1.2实验系统
  1.2.1 冷热源
  该实验的冷热源为空气源热泵机组。冷热源与毛细管网末端中间设置换热水箱,通过换热水箱控制供水温度为18℃。原理图如图2所示。
  
  1.2.2实验末端
  实验的末端为顶棚、墙面、地面3种敷设方式,房间410顶棚、墙面敷设同侧供回S型毛细管网,房间412地面敷设同侧供回S型毛细管网。实验室建设时,为满足室内冷负荷需求,设置如下毛细管网参数见表1。
  
  1.2.3新风系统 实验新风温度为24℃,相对湿度为60%,新风量为60m3/h,新风送风方式为上送风。
  1.3实验内容
  1.3.1测试方案 实验系统运行工况见表2,根据《辐射供暖供冷技术规程JGJ142-2012》中规定:毛细管网供水温度应保证供冷表面温度高于露点温度1℃ ~ 2℃。故本次实验在18℃供水温度下,测试毛细管网顶棚、墙面、地面3种敷设方式的室内热工参数。
  1.3.2测点布置 实验测点[18]的布置原则参照《民用建筑室内热湿环境评价标准GB/T50785-2012》中的规定,详见图5、图6。实验数据采用实时监测,记录间隔为10min/次。
  实验房间围护结构表面温度测点布置如下:顶棚布置5个,地面布置5个,左墙布置9个,右墙布置9个,外墙布置2个,内墙布置2个,共计32个。
  实验房间空间温度测点布置如下:在图5中a、b、c、d、e位置上距地0.1m(脚踝)、0.6m(膝蓋)、1.1m(坐姿头部)、1.7m(站姿头部)、2.5m(房间上空)处,共计25个。空间湿度测点布置如下:在a、c、e位置距地1.1m高度处,共计3个。
  1.3.3测试仪器 实验主要仪器如下表3所示:
  2实验数据分析
  2.1室外空气温度
  实验期间室外逐时温度见图7。顶棚、墙面、地面3种敷设方式室外平均温度依次为29.97℃、31.26℃、29.97℃。
  
  
  2.2室内人员活动区平均温度
  人员活动区平均温度为a、b、c、d、e 五个水平位置分别距地0.1m、0.6m、1.1m、1.7m四个垂直高度的20个测点平均值。3种敷设方式实验期间人员活动区逐时温度见图8,由图可知:
  1)毛细管网地面辐射供冷时,人员活动区温度达到28℃响应时间最长。顶棚、墙面、地面3种敷设方式响应时间依次为:20min、50min、60min。
  2)3种敷设方式人员活动区平均温度均满足≤28℃要求,顶棚、墙面、地面3种敷设方式供冷稳定时人员活动区的平均温度依次为:26.27℃,27.22℃,26.57℃。
  3)人员活动区温度的影响因素主要包括以下两个方面:辐射壁面温度与距辐射壁面距离。顶棚敷设毛细管网,由于其敷设构造较薄,辐射壁面温度低,因此供冷稳定时室内温度低于另外两种敷设方式;墙面敷设毛细管网,由于其敷设单面,冷空气横向传播速度慢,因此供冷稳定时室内温度高于另外两种敷设方式;地面敷设毛细管网,虽然其辐射壁面温度较另外两种敷设方式高,但是距离人员活动区最近,因此稳定时室内温度与顶棚敷设时温度接近。
  2.3室内人员活动区平均相对湿度
  人员活动区平均相对湿度为a、c、e点距地1.1m高度的相对湿度平均值,3种敷设方式人员活动区逐时平均相对湿度见图9,由图可知:
  顶棚、墙面、地面3种敷设方式人员活动区稳定时平均相对湿度均满足室内舒适要求。墙面敷设人员活动区平均相对湿度略小于顶棚、地面。平均相对湿度依次为68.58%、64.13%、70.05%。
  
  2.4露点温度分析
  3种敷设方式露点温度见图10,由图可知:
  顶棚、墙面、地面3种敷设方式的辐射壁面温度、附近空气温度均高于辐射壁面露点温度,因此实验过程中均未出现结露现象。但重庆地区湿度较大,为防止辐射供冷时出现结露,应设置通风除湿系统。
  
  2.5辐射壁面平均温度
  辐射壁面平均温度与毛细管网敷设构造密切相关。3种敷设方式辐射壁面逐时温度见图11,由图可知:
  1)毛细管网敷设构造越薄,辐射壁面热响应时间越快,辐射壁面温度也越低。顶棚、墙面、地面敷设构造厚度依次递增,热响应时间依次递增,辐射壁面平均温度也依次递增,依次为20.96℃,21.14℃,22.76℃。
  2)顶棚、墙面、地面3种敷设方式辐射壁面平均温度均满足《辐射供暖供冷技术规程JGJ142-2012》中的规定。具体要求值见表4。
  3)常规地盘管地面上部敷设构造厚度较厚,不宜用于毛细管网地面,为缩短地面辐射热响应时间,降低辐射壁面温度,可降低毛细管网地面敷设构造厚度。
  2.6围护结构壁面温度
  3种敷设方式围护结构壁面温度分布见图13,由图可知:
  1)3种敷设方式外墙温度高于其他壁面温度,由于外墙未做保温,故受室外温度影响较大。
  2)墙面、地面敷设毛细管网供冷时,顶棚壁面温度均较高。主要原因是热空气在房间上部堆积,减弱顶棚壁面降温。   3)3种敷设方式辐射角系数对壁面温度的影响较小。
  
  
  2.7空间垂直温度分析
  3种敷设方式垂直温度分布见图14,站姿高差为0.1m~1.7m,坐姿高差为0.1m~1.1m。由图可知:
  1)3种敷设方式供冷时,顶棚敷设垂直温差最小,且有“头凉脚暖”的感觉,舒适度最好。
  2)3种敷设方式供冷时,坐姿或站姿纵向温差均小于1℃,满足ISO7730[19]推荐的小于2℃(A级)的温差。
  
  2.8空间水平温度分析
  室内空间水平温度分析选取a、b、c、d、e距地1.1m处温度。3种敷设方式水平温度分布见图15,由图可知:
  1)墙面敷设毛细管网供冷时,水平温度分布最不均匀。为减弱单面墙供冷造成水平温度分布不均匀可两对面墙同时敷设。
  2)顶棚、墙面敷设毛细管网供冷时,d点的温度出现温升的主要原因是该点位于门口,实验状况记录人员进出房间时将内走廊热量带入房间造成。
  
  
  2.9 PMV、PPD分析
  由图16、17可知:
  1)顶棚、墙面、地面3种敷设方式供冷稳定时,PMV依次为-0.27,0.32,-0.2, PPD依次为7.06%,7.47%,6.34%。
  2)3种敷设方式供冷稳定阶段时,室内PMV、PPD均满足《民用建筑室内热湿环境评价标准GB/T50785-2012》I级热舒适评价指标-0.5≤PMV≤0.5,PPD≤10%[17]。
  3)3种敷设方式墙面辐射供冷时,室内舒适度最差。单面墙辐射供冷时,被降温的冷空气沿墙面下沉,在右墙下侧积聚,冷空气横向传递效果较差。因此墙面辐射供冷若想达到顶棚,地面辐射供冷效果,可通过增大毛细管网敷设面积、降低供水温度或增大管内流速等途径实现。
  
  3结论
  通过对比分析夏季毛细管网供冷室内环境,得出以下结论:
  1)毛细管网供水温度设定为18℃时,3种敷設方式辐射供冷,室内人员活动区平均温度均满足≤28℃的要求。供冷稳定阶段,顶棚、墙面、地面人员活动区平均温度依次为26.27℃,27.22℃,26.57℃
  2)毛细管网敷设构造越薄,辐射壁面热响应时间越快,辐射壁面温度也越低。顶棚、墙面、地面敷设构造厚度依次递增,热响应时间依次递增,辐射壁面平均温度也依次递增,依次为20.96℃,21.14℃,22.76℃。
  3)顶棚敷设毛细管网供冷时纵向温差明显低于墙面、地面,舒适度更高。3种敷设方式纵向均小于1℃,满足ISO 7730推荐的小于2℃(A级)温差。
  4)顶棚、地面敷设毛细管网供冷时室内水平效果接近,优于墙面。墙面敷设毛细管网供冷时,水平温度分布最不均匀。为减弱单面墙供冷造成水平温度分布不均匀可两对面墙同时敷设。
  5)3种敷设方式室内预计平均热感觉指数PMV,预计不满意者百分数PPD均满足《民用建筑室内热湿环境评价标准GB/T50785 -2012》I级热舒适评价指标-0.5≤PMV≤0.5,PPD≤10%,供冷稳定阶段,顶棚、墙面、地面PMV依次为-0.27,0.32,-0.2,PPD依次为7.06%,7.47%,6.34%。
  
  
  参考文献
  [1] H?SEGGEN R, MATHISEN H M, HANSSEN S O. The effect of suspended ceilings on energy performance and thermal comfort[J]. Energy and Buildings, 2009, 41(2): 234-245.
  [2] MIKESKA T, SVENDSEN S. Dynamic behavior of radiant cooling system based on capillary tubes in walls made of high performance concrete[J]. Energy and Buildings, 2015, 108: 92-100.[LinkOut]
  [3] FAUCHOUX M, BANSAL M, TALUKDAR P, et al. Testing and modelling of a novel ceiling panel for maintaining space relative humidity by moisture transfer[J]. International Journal of Heat and Mass Transfer, 2010, 53(19/20): 3961-3968.
  [4] KEBLAWI A, GHADDAR N, GHALI K. Model-based optimal supervisory control of chilled ceiling displacement ventilation system[J]. Energy and Buildings, 2011, 43(6): 1359-1370.[LinkOut]
  [5] LEE K G, HONG W H. Thermal-environment characteristics and comfort of combined radiant-floor (Korean heating system ondol) and convective cooling system [J]. Journal of Central South University. 2013, 20 (12): 3589 – 3603.   [5] LEE K G, HONG W H. Thermal-environment characteristics and comfort of combined radiant-floor (Korean heating system ondol) and convective cooling system[J]. Journal of Central South University, 2013, 20(12): 3589-3603.[LinkOut]
  [6] EUSEBIO Z. E, CONCECAON, MANUELA J R, et al. Evaluation of thermal comfort conditions in a classroom equipped with radiant cooling systems and subjected to uniform convective environment [J]. Applied Mathematical Modeling, 2011, 35(3): 1292-1305.
  [7] KYU N R , KWANG W K . A 50 year review of basic and applied research in radiant heating and cooling systems for the built environment [J]. Building and Environment, 2015,91:166-190.
  [8] 李炅,高珊,賈甲,等.毛细管辐射供冷系统性能的试验及数值模拟研究[J].制冷技术,2014,34(4):18-22.
  LI J, GAO S, JIA J, et al. Experimental and
  numerical simulation study on the performance of
  capillary radiation cooling system[J] . Journal of Refrigeration Technology, 2014, 34
  (4): 18-22.
  [9] 朱备, 翟晓强, 尹亚领, 等. 毛细管辐射供冷的换热及结露特性的实验研究[J]. 制冷技术, 2013, 33(4): 5-10.ZHU B,ZHAI X Q,YIN Y L, et al. Experimental investigation of heat transfer and dew performances of capillary radiant cooling[J]. Chinese Journal of Refrigeration Technology, 2013, 33(4): 5-10.(in Chinese)
  [10] 谢东, 王赟, 廖买利, 等. 基于不同管径毛细管辐射顶板供冷性能模拟[J]. 建筑热能通风空调, 2016, 35(11): 1-4,48.XIE D, WANG Y, LIAO M L, et al. Numerical modeling of cooling performance for capillary ceiling radiant cooling panel based on pipe diameters[J]. Building Energy & Environment, 2016, 35(11): 1-4,48.(in Chinese)
  [11] 王赟, 谢东, 莫顺权, 等. 毛细管辐射冷却顶板供冷性能的数值模拟研究[J]. 制冷与空调(四川), 2016, 30(3): 287-290,294.WANG Y,XIE D,MO S Q, et al. Numerical modeling on cooling performance of capillary ceiling radiant cooling panel[J]. Refrigeration & Air Conditioning, 2016, 30(3): 287-290,294.(in Chinese)
  [12] 张金明. 壁面辐射供冷与独立新风复合空调的数值模拟研究[D]. 西安: 西安科技大学, 2015. ZHANG J M. The numerical simulation research of the wall radiant cooling air conditioning system with independent fresh air[D]. Xi'an: Xi'an University of Science and Technology, 2015.(in Chinese)
  [13] 刘猛, 王旭弟, Liu Meng, 等. 湿热地区毛细管地板供冷末端性能实测分析[J]. 土木建筑与环境工程, 2017, 39(1): 1-6.LIU M, WANG X D, LIU M, et al. Experimental analysis of terminal performance for floor cooling with capillary tubes in hot-humid area[J]. Journal of Civil,Architectural & Environmental Engineering, 2017, 39(1): 1-6.(in Chinese)
  [14] 李妍, 许彬, 贾军华, 等. 毛细管网抹灰安装供冷能力分析[J]. 暖通空调, 2017, 47(1): 97-102.LI Y, XU B, JIA J H, et al. Cooling capacity analysis of capillary network with plasterer paving[J]. Heating Ventilating & Air Conditioning, 2017, 47(1): 97-102.(in Chinese)   [15] 陈金华, 杨雯芳, 沈雪莲, 等. 不同供水工况毛细管网地板辐射供暖实验研究[J]. 湖南大学学报(自然科学版), 2017, 44(11): 205-212.CHEN J H, YANG W F, SHEN X L, et al. Experimental research on capillary floor radiant heating in different water supply temperature[J]. Journal of Hunan University(Natural Sciences), 2017, 44(11): 205-212.(in Chinese)
  [16] 陈露, 廖胜明, CHEN Lu, 等. 三种方式辐射供冷室内热环境对比分析[J]. 建筑热能通风空调, 2010, 29(3): 53-56.CHEN L, LIAO S M, CHEN L, et al. Three approaches to the comparative study of indoor thermal environment for radiant cooling system[J]. Building Energy & Environment, 2010, 29(3): 53-56.(in Chinese)
  [17] 梁秋锦. 毛细管网不同敷设方式供冷性能研究[D]. 重庆: 重庆大学, 2017.LIANG Q J. Study on cooling performance with capillary different laying ways[D]. Chongqing: Chongqing University, 2017.(in Chinese)
  [18] 陈金华, 梁秋锦, 李楠, 等. 毛细管网供暖室内环境对比实验研究[J]. 土木建筑与环境工程, 2018, 40(2): 88-94.CHEN J H, LIANG Q J, LI N, et al. Comparative experimental analysis of capillary radiant heating on indoor environment[J]. Journal of Civil,Architectural & Environmental Engineering, 2018, 40(2): 88-94.(in Chinese)
  [19] ★★★, ★★★. Moderate thermal environments. Determination of the PMV and PPD indices and specification of the conditions for thermal comfort[S]. BSI British Standards, . DOI:10.3403/00814151
  [20] GB 50736-2012《民用建筑供暖通風及空气调节设计规范》[S].北京:中国建筑工业出版社,2012.  GB 50736-2012 Regulations on the design of heating ventilation and air conditioning for civil buildings [S]. Beijing: China Architecture and Building Press, 2012.
  
  (编辑:邓云)
  
  
  
  
  
  
  
  
  
  
  
  
其他文献
摘要:中国面板坝建设规模正突破200~300m级跨越,研究地震面板损伤破坏对特高坝抗震性能和安全控制具有重要意义。引入Quadtree跨尺度建模和非线性SBFEM-FEM耦合分析方法,联合土体广义塑性模型、弹塑性接触模型和混凝土塑性损伤模型,研究了高面板坝面板地震精细损伤演化过程。研究表明:面板損伤区主要发生在高程0.6H~0.9H区间附近;随顺坡向网格细化,损伤越趋局部化,越能合理地反映面板顶部
期刊
摘要:在城市建设中,深基坑开挖会对邻近既有地下管线产生较大威胁。目前,基于有限元数值模拟和传统弹性地基梁模型分析方法无法考虑由于管线与土体之间刚度和变形的差异性而造成的管一土相互分离现象,使得对于基坑开挖引起管线变形的预测偏于不安全。基于Pasternak弹性地基梁理论,引入管一土相互分离计算模型,推导了基坑开挖引起的邻近管线变形计算解析解。参数分析结果表明,管线最大位移随管一土分离段长度的增大而
期刊
摘要:  为了研究铸钢节点对接焊缝的疲劳性能和寿命评估方法,对一种常用的铸钢热轧钢对接焊缝试件进行了疲劳试验研究,得到了刚度、位移与疲劳寿命阶段之间的关系。根据疲劳试验现象和断面的电镜扫描结果,提出了该类试件的疲劳失效机理。此外,采用有效缺口应力法预测了铸钢节点对接焊缝的疲劳寿命,并在考虑了平均应力和焊接残余应力的前提下,提出了改进的有效缺口应力法,分别将预测结果与实测疲劳寿命进行了对比。研究结果
期刊
摘 要:收集了世界不同地区304组海洋潮汐浪溅区混凝土的自然暴露的试验数据,据此分析了水胶比、胶凝材料种类和暴露时间对混凝土表面氯离子浓度Cs,ts的影响规律,进而结合二阶段多元非线性回归分析,分别确定了硅酸盐水泥、粉煤灰、矿渣和硅灰等胶凝材料对Cs,ts的修正系数,建立了海洋潮汐浪溅区Cs,ts的改进模型,并利用现有模型和试验数据对比,验证了该模型的适用性。分析表明:Cs,ts与水胶比之间近似呈
期刊
摘 要:寒区冻融环境条件下,尾矿砂的冻融、缩胀、损伤破坏给寒区尾矿坝工程造成极大的危害。为探究冻融循环作用下尾矿坝变形规律,揭示其变形机制。采用自主设计的尾矿坝相似模型试验装置,开展不同冻结温度(-5、-25、-45 ℃)条件下,尾矿坝的变形规律模型试验。借助土压力、激光位移、孔隙水压力传感器,采用动态数据采集仪采集相关数据,分析冻融循环过程中尾矿坝各关键位置应力、变形、孔隙水压力的动态变化规律。
期刊
摘 要:针对余氯量在供水系统内非线性变化特性,建立了PSO-SVM+BP神经网络组合模型对管网末端余氯进行预测分析。该模型通过粒子群优化算法(PSO),对SVM的特性参数进行优化;采用BP神经网络对模型进行残差修正。本文通过对比BP和SVM单一预测、对组合模型预测精度进行分析。结果表明:组合模型预测比BP和SVM单一预测均方误差分别降低了62.30%、75.29%,平均相对误差降低了55.03%、
期刊
摘 要:针对沙漠地区砂土地基的工程特性及现有输电塔基础存在的不足,研发出索连板球基础,该基础既填补了沙漠地区输电塔基础的空白,克服了砂土地基基础施工难题,又满足了工程安全稳定性要求。通过室内相似模型上拔试验与数值模拟计算相结合,对不同上拔荷载作用下的基础位移进行了分析,同时研究了埋深比、球径及柱径对基础极限抗拔承载力系数及土体表面主破裂面半径的影响及其规律。研究结果表明:数值模拟计算结果与模型试验
期刊
摘 要:考虑超静孔隙水压作用的软土卸荷力学特性对于富水软土地区地下空间开挖变形和稳定性的分析具有重要作用。以深圳地区淤泥质软土为研究对象,开展不同初始超静孔隙水压作用下的K0固结不排水三轴卸荷强度试验和卸荷蠕变试驗。试验结果表明:初始超静孔隙水压越大,固结围压越小,软土卸荷破坏就更具有突然性;软土卸荷强度应力-应变曲线大致呈双曲线型,其双曲线函数拟合结果表明,卸荷强度随着初始超静孔隙水压的增大而大
期刊
摘要 随着建筑围护结构保温性能的逐步提高,以室内人员为代表的内部因素已成为影响建筑负荷的重要不确定性因素,内部负荷扰量(简称内扰)在空调负荷设计中的重要性需要被强调。通过对两栋办公建筑的实地测试,发现办公建筑中人员在室率普遍只有设计人数的40%~60%,设备实际功率也远低于20 W/m2的概算指标,过大的经验值是造成机组选型偏大的重要原因。重新思考标准中的人员密度系数和设备使用密度系数,以人为核心
期刊
摘 要:以羧甲基壳聚糖(CMCTS)为主链模板、丙烯酰胺(AM)和甲基丙烯酰氧乙基三甲基氯化铵(DMC)为共聚单体,通过紫外光引发聚合法制备新型阳离子絮凝剂CMCTS-g-CPAM。并采用响应曲面法(RSM)得到CMCTS-g-CPAM的最佳制备条件:光照时间为2h、光引发剂质量分数为0.04%、pH为8。接枝共聚物CMCTS-g-CPAM的红外光谱(FT-IR)和核磁共振(1H-NMR)表征表明
期刊