论文部分内容阅读
在工业生产中,使用玻璃钢冷却塔降低水温有很多优点,受到工业企业的青睐。但它也有一个大缺点,即在安装施工动火过程中,易发生火灾。同类事故重复发生 1993年3月14日,辽宁某化工厂在玻璃钢冷却塔安装施工过程中,因电焊火花落到塔内聚丙烯波纹片上,引起着火,仅十几分钟,冷却塔全部烧毁,直接经济损失1.9万元。10年后的2003年7月27日,由于同样原因,该冷却塔又被全部烧毁,直接经济损失3万余元。同类事故还发生在湖北、上海等地厂家。玻璃钢冷却塔发生的火灾有时还会造成相关设备和厂房的火灾,经济损失少则几万元,多则数十万元。
In industrial production, the use of fiberglass cooling towers to reduce water temperature has many advantages, favored by the industrial enterprises. But it also has a big disadvantage, that is, in the process of installing and installing a moving fire, it is easy to have a fire. Repetition of similar accidents March 14, 1993, a chemical plant in Liaoning in the installation of glass fiber reinforced plastic cooling tower construction process, due to welding sparks falling into the tower corrugated polypropylene sheet, causing the fire, only ten minutes, all the cooling towers were burned directly Economic loss of 19,000 yuan. Ten years later, on July 27, 2003, for the same reason, the cooling tower was completely destroyed, with a direct economic loss of more than 30,000 yuan. Similar accidents also occurred in Hubei, Shanghai and other manufacturers. FRP cooling tower fire sometimes can cause fires related equipment and plant, the economic loss of less than tens of thousands of dollars, as many as several hundred thousand dollars.