论文部分内容阅读
摘要:建筑混凝土检测是确定新建和已建建筑混凝土结构或构件承载能力等力学性能的关键因素,建筑混凝土强度检测技术是工程结构检测中非常重要的一项内容,分为非破损检测和局部破损检测。建筑混凝土表面硬度,是一个与建筑混凝土强度有关的多种因素之一,回弹法作为一种检测硅抗压强度的手段,因其检测仪器的轻便、灵活、精度高,检测方法的统一,抽取子样的代表性高等优点,在工程检测中得到了广泛的应用。文章对建筑混凝土检测中常用的非破损检测法———回弹法进行了阐述分析。
关键词:回弹法;非破损检测法;建筑混凝土;质量检测;检测结果评定
Abstract: Building concrete detection is a key factor to determine the new and existing building concrete structures or members carrying capacity and mechanical properties, intensity detection technology of concrete building is an important content of engineering structure detection, divided into non destructive inspection and local damage detection. Construction of concrete surface hardness, is one related to the construction of concrete strength of various factors, the rebound method as a means of detecting silicon compressive strength, because of its detection instrument light, flexible, high precision, unified detection method, representative high extraction samples, obtained the widespread application in engineering detection in. The concrete building detection is commonly used in nondestructive testing method -- the rebound method is analyzed.
Key words: rebound method; nondestructive testing; concrete construction; quality inspection; evaluation of test results
中图分类号:TJ765.4
一、检测目的与方法
检测依据根据《回弹法检测建筑混凝土抗压强度技术规程》,回弹法是通过回弹仪器测定建筑混凝土表面硬度继而推定其抗压强度。
按批检测:在相同的生产条件、相同的建筑混凝土强度等级,原材料、配合比、成型工艺、养护:条件基本一致,且龄期相近的同类构件,不得少于该批构件总数的30%,且测区数量不得少于l00个。按单个构件检测:对长度不小于3m的构件,其测区不少于10个,对长度小于3m,且高度小于0.6m的构件,其测区数量可适当减少,但不应少于5个。需钻取建筑混凝土芯样对回弹值进行修正时,芯样试件数量不少于3个。
必须使用有检定合格证书的回弹仪。在检测前,需在20±5℃的室温条件下对回弹仪按标准方法在钢砧上进行率定。其率定平均值应符合80±2的要求。回弹仪使用时的环境温度为- 4℃~+40℃。
检测前应检查建筑混凝土表面是否清洁、平整,不应有疏松、浮浆、油垢以及蜂窝、麻面,必要时可用砂轮清除疏松层和杂物,且不应有残留的粉末或粉屑。检测面应为原状建筑混凝土面。当检测条件与测强曲线的适用条件有较大差异时,可采用同条件试块或钻取建筑混凝土芯样进行修正。
回弹测点宜在测区范围内均匀分布,相邻两测点的净距一般不小于20mm,测点距构件边缘或外露钢筋、预埋件的距离一般不小于30mm。测点不应在气孔或外露石子上,同一测点只允许弹击一次,每一测区应记取16个回弹值,每一测点的回弹值读数精确至1。规范对相邻测区的间距,测区的面积、回弹仪的使用方向、施压方法、碳化深度值的测量等均作了明确规定。
二、检测结果评定
计算测区平均回弹值时,应从该测区的16个回弹值中剔除3个最大值和3个最小值,再将余下的10个回弹值按相关公式计算。
采用全国统一测强曲线计算建筑混凝土强度换算值时,被测建筑混凝土应符合下列条件:(1)符合普通建筑混凝土用材料、拌和用水的质量标准,粗骨料敞径<60mm;(2)不掺外加剂或仅掺非引气型外加剂;(3)采用普通成型工艺(加压、离心等不适用);(4)采用符合标准的模板;(5)龄期为14~1000d;(6)自然养护或蒸汽养护出池后,经自然养护7d以上,且建筑混凝土表层為干燥状态;(7)设计建筑混凝土抗压强度为10~50MPa。对统一曲线,其强度误差值为平均相对误差δ≤土15.0%;相对标准差Δy≤l8.0%。
经查表求得的建筑混凝土强度换算值,通过计算可得出结构或构件建筑混凝土的强度平均值。当测区数不少于10个时,还应计算强度标准差(按公式),当按单个构件检测时,以最小值作为该构件的建筑混凝土强度推定值,当按批量检测时,应按下列公式计算:
取以上二个公式中较大值为该构件的建筑混凝土强度推定值。
当该批构件建筑混凝土强度标准差出现下列情况之一时,则该批构件应全部按单个构件检测:
当该批构件建筑混凝土强度平均值小于25MPa时:Sfcuc>4.5MPa;
当该批构件建筑混凝土强度平均值不小于25MPa时:Sfcuc>5.5MPa。
另外,国家标准虽给出了全国通用回弹法检测的测强曲线并由此得到测定建筑混凝土强度值换算表,但全国统一曲线仅综合考虑到全国各地的原材料使用情况,没有把碎、卵石普通建筑混凝土区分开来,而实际上回弹法检测碎、卵石普通建筑混凝土强度是有很大差异的。而地区测强曲线正是充分考虑本地区的建筑混凝土原材料、气候条件和成型养护工艺,通过试验、校核、修正所建立的曲线,与通用测强曲线相比较,该曲线比通用测强曲线更接近实验数据,能更好的推算本地区建筑混凝土的实际强度。因此,建立本地区的专用测强曲线,能有效地提高回弹法的检测精度。
三、报告审核
应按规范要求审核报告的基本格式,其中较为重要的是审阅平均强度值、标准差、最小测区强度值(必要时需要求列出构件测区布置示意图及其强度值),以及强度推定值。
结构或构件建筑混凝土强度的检测报告,应按规范要求审核报告的基本格式,其中较为重要的是审阅平均强度包括下列主要内容:建设单位;委托单位;施工单位;设计单位;工程名称和结构或构件名称;施工日期;检测原因;检测环境;检测依据(所用标准名称及编号);回弹仪生产厂家、型号、出厂编号及检定证号;结构或构件的平均强度值、标准差、最小测区强度值(必要时列出构件测区布置示意图及其强度值)及强度推定值;出具报告的单位名称(盖建筑混凝土非破损检测报告专用章)、审核人、检测负责人、试验员的姓名及资质;)检测及出具报告的日期;其他需要说明的事项。对于无法用文字表达清楚的内容,应附简图。
回弹法检测的结果是强度推定值,规范规定不允许用回弹检测取代建筑混凝土试件的制作,只是在对构件建筑混凝土强度有怀疑时使用。正常情况下建筑混凝土强度检测应以国家标准《建筑混凝土结构工程施工及验收规程》及《建筑混凝土强度检验评定标准》执行。
回弹法检测建筑混凝土强度的前提,是要求被测结构或构件的建筑混凝土内外质量基本一致,如果发现现场建筑混凝土表层与内部质量有明显差异,如遭受化学腐蚀、火灾、冻伤或内部存在缺陷时;建筑混凝土硬化期间遭受冻伤等内部存在缺陷时,不允许使用此方法。
四、检测注意事项
在实际检测中,检测人员应严格按照标准规定的技术要求进行检测操作,提高回弹法的检测精度。仪器使用完毕后,要及时对回弹仪进行必要和细心的养护。
回弹仪的质量及测试性能直接影响建筑混凝土强度推定的准确性,只有性能良好的回弹仪才能保证测试结果的可靠性。用于回弹检测的建筑混凝土构件,表面应清洁、平整,不应有疏松层、浮浆、油垢、蜂窝、麻面。在检测时经常遇到麻面或有浮浆的构件,回弹前必须用砂轮磨平,否则结果偏低。
回弹法测强得到的建筑混凝土强度推定值,不能参加强度评定。《建筑混凝土结构工程施工及验收规范》(GB50204- 2002)(2010年版)第7.1.4条规定:当建筑混凝土试件强度评定不合格时,可采用非破损或局部破损的检测方法,按国家现行有关标准的规定对结构构件中的建筑混凝土强度进行推定,并作为处理的依据。同时该规范要求评定结构构件的建筑混凝土强度应采用标准试件的建筑混凝土强度,即按标准方法制作的边长为150mm的标准尺寸的立方体试件,在温度为20±3℃,相对湿度为90%以上的环境或水中的标准条件下,养护至28d龄期时按标准试验方法测得的建筑混凝土立方体抗压强度標准值。
所以,用回弹法测得的建筑混凝土强度换算值、平均值、标准差及强度推定值不能参加建筑混凝土抗压强度的评定。只能作为是否应进行处理的依据。
参考文献:
[1] 邓建刚,卢华.预拌混凝土所用砂质量的控制[J]. 西北水力发电. 2005(S2)
[2] 高祖光.商品混凝土的质量现状与施工过程检测的重要性[J]. 科学之友(B版). 2007(01)
[3] 吴立荣.水泥混凝土施工的质量控制[J]. 科技创新导报. 2009(07)
[4] 赵竞.谈预拌混凝土生产的质量检测管理[J]. 辽宁建材. 2006(04)
关键词:回弹法;非破损检测法;建筑混凝土;质量检测;检测结果评定
Abstract: Building concrete detection is a key factor to determine the new and existing building concrete structures or members carrying capacity and mechanical properties, intensity detection technology of concrete building is an important content of engineering structure detection, divided into non destructive inspection and local damage detection. Construction of concrete surface hardness, is one related to the construction of concrete strength of various factors, the rebound method as a means of detecting silicon compressive strength, because of its detection instrument light, flexible, high precision, unified detection method, representative high extraction samples, obtained the widespread application in engineering detection in. The concrete building detection is commonly used in nondestructive testing method -- the rebound method is analyzed.
Key words: rebound method; nondestructive testing; concrete construction; quality inspection; evaluation of test results
中图分类号:TJ765.4
一、检测目的与方法
检测依据根据《回弹法检测建筑混凝土抗压强度技术规程》,回弹法是通过回弹仪器测定建筑混凝土表面硬度继而推定其抗压强度。
按批检测:在相同的生产条件、相同的建筑混凝土强度等级,原材料、配合比、成型工艺、养护:条件基本一致,且龄期相近的同类构件,不得少于该批构件总数的30%,且测区数量不得少于l00个。按单个构件检测:对长度不小于3m的构件,其测区不少于10个,对长度小于3m,且高度小于0.6m的构件,其测区数量可适当减少,但不应少于5个。需钻取建筑混凝土芯样对回弹值进行修正时,芯样试件数量不少于3个。
必须使用有检定合格证书的回弹仪。在检测前,需在20±5℃的室温条件下对回弹仪按标准方法在钢砧上进行率定。其率定平均值应符合80±2的要求。回弹仪使用时的环境温度为- 4℃~+40℃。
检测前应检查建筑混凝土表面是否清洁、平整,不应有疏松、浮浆、油垢以及蜂窝、麻面,必要时可用砂轮清除疏松层和杂物,且不应有残留的粉末或粉屑。检测面应为原状建筑混凝土面。当检测条件与测强曲线的适用条件有较大差异时,可采用同条件试块或钻取建筑混凝土芯样进行修正。
回弹测点宜在测区范围内均匀分布,相邻两测点的净距一般不小于20mm,测点距构件边缘或外露钢筋、预埋件的距离一般不小于30mm。测点不应在气孔或外露石子上,同一测点只允许弹击一次,每一测区应记取16个回弹值,每一测点的回弹值读数精确至1。规范对相邻测区的间距,测区的面积、回弹仪的使用方向、施压方法、碳化深度值的测量等均作了明确规定。
二、检测结果评定
计算测区平均回弹值时,应从该测区的16个回弹值中剔除3个最大值和3个最小值,再将余下的10个回弹值按相关公式计算。
采用全国统一测强曲线计算建筑混凝土强度换算值时,被测建筑混凝土应符合下列条件:(1)符合普通建筑混凝土用材料、拌和用水的质量标准,粗骨料敞径<60mm;(2)不掺外加剂或仅掺非引气型外加剂;(3)采用普通成型工艺(加压、离心等不适用);(4)采用符合标准的模板;(5)龄期为14~1000d;(6)自然养护或蒸汽养护出池后,经自然养护7d以上,且建筑混凝土表层為干燥状态;(7)设计建筑混凝土抗压强度为10~50MPa。对统一曲线,其强度误差值为平均相对误差δ≤土15.0%;相对标准差Δy≤l8.0%。
经查表求得的建筑混凝土强度换算值,通过计算可得出结构或构件建筑混凝土的强度平均值。当测区数不少于10个时,还应计算强度标准差(按公式),当按单个构件检测时,以最小值作为该构件的建筑混凝土强度推定值,当按批量检测时,应按下列公式计算:
取以上二个公式中较大值为该构件的建筑混凝土强度推定值。
当该批构件建筑混凝土强度标准差出现下列情况之一时,则该批构件应全部按单个构件检测:
当该批构件建筑混凝土强度平均值小于25MPa时:Sfcuc>4.5MPa;
当该批构件建筑混凝土强度平均值不小于25MPa时:Sfcuc>5.5MPa。
另外,国家标准虽给出了全国通用回弹法检测的测强曲线并由此得到测定建筑混凝土强度值换算表,但全国统一曲线仅综合考虑到全国各地的原材料使用情况,没有把碎、卵石普通建筑混凝土区分开来,而实际上回弹法检测碎、卵石普通建筑混凝土强度是有很大差异的。而地区测强曲线正是充分考虑本地区的建筑混凝土原材料、气候条件和成型养护工艺,通过试验、校核、修正所建立的曲线,与通用测强曲线相比较,该曲线比通用测强曲线更接近实验数据,能更好的推算本地区建筑混凝土的实际强度。因此,建立本地区的专用测强曲线,能有效地提高回弹法的检测精度。
三、报告审核
应按规范要求审核报告的基本格式,其中较为重要的是审阅平均强度值、标准差、最小测区强度值(必要时需要求列出构件测区布置示意图及其强度值),以及强度推定值。
结构或构件建筑混凝土强度的检测报告,应按规范要求审核报告的基本格式,其中较为重要的是审阅平均强度包括下列主要内容:建设单位;委托单位;施工单位;设计单位;工程名称和结构或构件名称;施工日期;检测原因;检测环境;检测依据(所用标准名称及编号);回弹仪生产厂家、型号、出厂编号及检定证号;结构或构件的平均强度值、标准差、最小测区强度值(必要时列出构件测区布置示意图及其强度值)及强度推定值;出具报告的单位名称(盖建筑混凝土非破损检测报告专用章)、审核人、检测负责人、试验员的姓名及资质;)检测及出具报告的日期;其他需要说明的事项。对于无法用文字表达清楚的内容,应附简图。
回弹法检测的结果是强度推定值,规范规定不允许用回弹检测取代建筑混凝土试件的制作,只是在对构件建筑混凝土强度有怀疑时使用。正常情况下建筑混凝土强度检测应以国家标准《建筑混凝土结构工程施工及验收规程》及《建筑混凝土强度检验评定标准》执行。
回弹法检测建筑混凝土强度的前提,是要求被测结构或构件的建筑混凝土内外质量基本一致,如果发现现场建筑混凝土表层与内部质量有明显差异,如遭受化学腐蚀、火灾、冻伤或内部存在缺陷时;建筑混凝土硬化期间遭受冻伤等内部存在缺陷时,不允许使用此方法。
四、检测注意事项
在实际检测中,检测人员应严格按照标准规定的技术要求进行检测操作,提高回弹法的检测精度。仪器使用完毕后,要及时对回弹仪进行必要和细心的养护。
回弹仪的质量及测试性能直接影响建筑混凝土强度推定的准确性,只有性能良好的回弹仪才能保证测试结果的可靠性。用于回弹检测的建筑混凝土构件,表面应清洁、平整,不应有疏松层、浮浆、油垢、蜂窝、麻面。在检测时经常遇到麻面或有浮浆的构件,回弹前必须用砂轮磨平,否则结果偏低。
回弹法测强得到的建筑混凝土强度推定值,不能参加强度评定。《建筑混凝土结构工程施工及验收规范》(GB50204- 2002)(2010年版)第7.1.4条规定:当建筑混凝土试件强度评定不合格时,可采用非破损或局部破损的检测方法,按国家现行有关标准的规定对结构构件中的建筑混凝土强度进行推定,并作为处理的依据。同时该规范要求评定结构构件的建筑混凝土强度应采用标准试件的建筑混凝土强度,即按标准方法制作的边长为150mm的标准尺寸的立方体试件,在温度为20±3℃,相对湿度为90%以上的环境或水中的标准条件下,养护至28d龄期时按标准试验方法测得的建筑混凝土立方体抗压强度標准值。
所以,用回弹法测得的建筑混凝土强度换算值、平均值、标准差及强度推定值不能参加建筑混凝土抗压强度的评定。只能作为是否应进行处理的依据。
参考文献:
[1] 邓建刚,卢华.预拌混凝土所用砂质量的控制[J]. 西北水力发电. 2005(S2)
[2] 高祖光.商品混凝土的质量现状与施工过程检测的重要性[J]. 科学之友(B版). 2007(01)
[3] 吴立荣.水泥混凝土施工的质量控制[J]. 科技创新导报. 2009(07)
[4] 赵竞.谈预拌混凝土生产的质量检测管理[J]. 辽宁建材. 2006(04)