御南热力站存在严重的水力失调、各用户用热不均现象,同时热力站热耗、电耗大,运行不经济等问题.采用流量法对供热管网进行调整,降低不平衡率;采用改变变频泵频率的方法对循环泵进行实验,探讨该小区合适的流量调频范围.实验结果表明,通过流量法调节系统管网,整个管网不平衡率由调整前的52%降低为调整后的8%,该热力站循环泵、加压泵选型较大,不利于系统的节能运行,建议对热力站循环泵、加压泵进行重新选型,以达到节能运行的目的.
YuNan thermal station has serious hydraulic imbalance, the user with the heat uneven phenomenon, at the same time heat station heat consumption, power consumption, operating uneconomical and other issues.Adopting flow method to adjust the heating pipe network, reducing the imbalance rate; The method of changing the frequency of the variable frequency pump was used to test the circulation pump and discuss the suitable range of the frequency modulation in the district.The experimental results show that by adjusting the system pipe network by flow method, the imbalance rate of the whole pipe network is reduced from 52% Of the 8%, the heat station circulating pump, pressure pump selection is larger, is not conducive to the system’s energy-saving operation, it is recommended to heat station circulating pump, pressurized pump re-selection, in order to achieve the purpose of energy-saving operation.