Hearth tank water temperature automatic detection system was successfully developed in Benxi Iron and Steel in 1989. The on-line operation of Bengang No.5 blast furnace for 7 consecutive months from October 20, 1989 to April 25, 1990 showed that the system has stable operation, reliable performance and high precision, which meets the requirements of the blast furnace production process. The system is composed of four parts: temperature sensor, conversion circuit, signal acquisition and industrial process control microcomputer. The design of temperature sensor is the key in the system. Bengang blast furnace hearth cooling water pressure is generally between 0.5 ~ 0.6MPa, the temperature range of about 7 ~ 37 ℃, and poor water quality, strong electromagnetic interference, long signal transmission distance (usually about 150m), so the temperature sensor is required to compare strict. To this end, the use of a high stability of the passive temperature sensing element, the accuracy of 0.2, a resolution of 0.01 degrees. Use 0.02mm thin-walled stainless steel tube as temperature sensing element