内翅片管换热器使用一段时间后,换热效率会降低。主要原因是:波纹型翅片与内管定位不好,引起管内堵塞;内管一端封头的头部很薄,使用一段时间后出现中孔现象,使流体短路,换热系数发生变化;内(外)管和翅片清洗不彻底,使内翅片换热管钎焊部位脱落,影响钎焊质量甚至堵塞通道。详细介绍在内翅片换热管加工过程中对上述三种问题的解决方法。
After using the inner fin tube heat exchanger for a period of time, the heat exchange efficiency will be reduced. The main reason is: corrugated fins and inner tube positioning is not good, causing the tube blockage; one end of the inner tube head is thin, the use of medium-bore phenomenon after a period of time, the fluid short circuit, the heat transfer coefficient changes; (Outside) the tube and fin cleaning is not complete, so that the internal fin heat exchanger soldered parts off, affecting the quality of brazing or even blocked the channel. Described in detail in the finned tube heat exchanger in the process of solving the above three problems.