2011年8月对安徽一家索道公司的客运索道进行监督检验,检验现场索道不能正常运行。根据索道公司技术人员对设备故障现象的描述和检验组现场勘查,对设备故障原因进行分析和故障排除。1故障现象检验当天索道公司派技术人员对索道进行运行试验时发现:在开关柜合主回路开关、控制电源开关、辅助电源开关时,1#整流模块一通电就出现“F068”故障代码且不能复位(当时是1#模块运行,2#模块备用)。在进行故障代码“F068”复位操作时又出现了故障代码“F040”且不能复位,断电后换至2#模块试看故障代码显示情况,闭合主回路和控
In August 2011, the Company conducted supervision and inspection on the passenger ropeway of a cableway company in Anhui Province, which failed to verify the normal operation of the cableway on site. According to the ropeway company’s technical staff description of the phenomenon of equipment failure and site inspection team inspection, equipment failure causes analysis and troubleshooting. Fault phenomenon test day ropeway company sent technicians to run the cable test found that: in the switchgear together with the main circuit switch, control the power switch, auxiliary power switch, 1 # rectifier module on power “F068” fault code And can not be reset (it is 1 # module running, 2 # module standby). The fault code “F040 ” appeared again during fault code “F068” reset and can not be reset. After power off, change to 2 # module to see the fault code display, close the main circuit and control