淮北发电厂~#5、~#6炉系东方锅炉厂早期生产的DG670/140—4型超高压中间再热燃煤锅炉,配200MW汽轮发电机组,分别于1981年12月和1982年11月投产运行。~#6炉运行1203小时后,高温再热器在30天内连续四次发生爆管事故,其中两次属超温爆管,一次属安装焊口泄漏,一次为管子焊接的定位焊件焊缝咬边泄漏。有21根管因氧化严重和壁厚减薄而闷死;另有80根管用耐火塑料包复。同期检查发现~#5炉运行7132小时后,高温再热管出现大面积氧化现象,在每排下端向火面沿高度4m范围内,尤以1.5m范围更为严重。
The early stage DG670 / 140-4 EHV intermediate reheat coal-fired boilers in Huaibei Power Plant ~ # 5 and ~ # 6 furnaces are equipped with 200MW steam turbine generator sets, respectively in December 1981 and November 11 Month put into operation. ~ # 6 furnace operation 1203 hours later, the high temperature reheater burst occurred in four consecutive pipe accidents within 30 days, of which two are super-temperature pipe burst, once the installation of weld leakage, a welding seam positioning pipe weld Undercut leakage. There are 21 tubes due to severe oxidation and wall thickness thinning suffocate; another 80 tubes with refractory plastic wrap. Over the same period of inspection found ~ # 5 furnace operation 7132 hours, the high temperature reheat tube large area oxidation phenomenon, at the bottom of each row to the fire along the height of 4m range, especially in the 1.5m range even more serious.