广西玉林大容山水电厂的1台800kW同步发电机,采用可控硅励磁,其整流电路为三相半控桥式。1987年9月机组安装投入运行不久,出现了可控硅两相运行的故障。现将故障现象及处理方法介绍如下。(一) 故障现象从发电机空载建压到并网满载运行,机组工作正常。运行6h后,无功表指示下降。调节“电压整定”电位器,当其指示到满刻度时,自动调节器的控制信号电压已达最低值,无功仍不能增至额定。停机以后,对励磁系统进行开环调试,用万用表测量可控桥直流侧输出电压,发现输出直流电压能够在规定范围内正常调节。重新开机并网运行,几小时后,上述故
Guangxi Yulin Dayongshan Hydropower Plant 800kW a synchronous generator, the use of SCR excitation, the rectifier circuit for the three-phase half-controlled bridge. Shortly after commissioning the unit in September 1987, a two-phase thyristor operation failure occurred. Now the phenomenon of failure and treatment are described below. (A) the phenomenon of failure from the generator no-load pressure to the grid and full load operation, the unit is working properly. After running 6h, the reactive power meter indicates a decrease. Adjust the “voltage setting” potentiometer, when it indicates full scale, the automatic regulator control signal voltage has reached the minimum value, the reactive power still can not be increased to rated. After shutdown, the excitation system for open-loop debugging, with a multimeter to measure the controllable bridge DC output voltage and found that the output DC voltage can be regulated within the specified range. Reboot the grid operation, a few hours later, the above