洁净手术室通风空调系统的运行能耗在医院运行能耗中占有相当大的比例。以实地对比试验研究为手段,对I级洁净手术室截面风速限值是否存在下调空间进行比较研究。试验结果表明,手术室截面风速下调至0.22m/s后,虽然导致动态条件下手术区浮游菌浓度上升,但从术中感染控制的角度来看,上升幅度仍处于可控制、可接受的范围内。
Clean operating room ventilation and air conditioning system running energy consumption in hospital operation occupies a considerable proportion of energy consumption. To compare the experimental study with field as a means to compare whether there is room for reduction in the cross-section wind speed limit of Class I clean operating room. The experimental results show that although the reduction of the cross-sectional wind speed in the operating room to 0.22 m / s results in the increase of the concentration of the bacteria in the operating area under dynamic conditions, the increase is still within a controllable and acceptable range from the perspective of intraoperative infection control Inside.