南昌通信楼空调是我局首次采用的淋水式集中空调系统,于1983年夏季正式开通使用。空调系统正常运转时,在气温最高的8月,空调房间的温度为25~27℃,相对湿度不超过70%,主要参数达到设计要求,使用效果良好。一、空调系统的规模与形式南昌通信楼为五层建筑,面积为4000m~2,是近期2000门,终期4000门自动电话的通信枢纽。根据通信设备工艺要求,载波室、自动室、长途自动汇接室(预留)、电传室和电话所等机房设空调,空调总面积:近期约1100m~2,
The Nanchang Communication Building Air Conditioning System was the first time the water-splashing centralized air conditioning system was adopted by the Bureau. It was officially opened in the summer of 1983. When the air-conditioning system is in normal operation, in the month with the highest temperature in August, the temperature of the air-conditioned room is 25 to 27°C and the relative humidity does not exceed 70%. The main parameters meet the design requirements and the use effect is good. First, the size and form of air-conditioning system Nanchang Communication Building is a five-story building, an area of 4000m ~ 2, is the recent 2000, the terminal 4000 automatic telephone communications hub. According to the technical requirements of communication equipment, air conditioners are installed in computer rooms such as carrier rooms, automatic rooms, long-distance automatic tandem rooms (reserved), telex rooms, and telephone stations. The total area of air conditioners is approximately 1100m~2 in the near future.