介绍了巴基斯坦恰希玛C-2项目提升发电功率由325MWe到340MWe过程中更换了主给水调节阀,2013年4月开始对主给水调节阀进行调试,在调试的过程中,阀门在手动操作状态下出现超调和滞后现象,低功率工况下,流量波动为30T/H,无法投入运行。针对上述问题,现场组织安装单位,PAEC业主和秦山调试队进行了技术攻关,先后研究了大量历史数据和技术资料,对KMM控制系统和调节阀技术资料进行了研究,先后采取了更换了阀门气动放大器,对阀门管线密封性检查,反馈杆松动检查,更换阀门定位器,调整阀门气动放大器(继动器),调节阀门定位器PID参数,消除阀门阀杆的摩擦力等方式进行了调试,最终消除了缺陷。本文主要针对主给水调节阀在调试过程中发生的故障现象、采取的措施及效果进行了分析。
Introduced the Pakistan Cha Xi Ma C-2 project to upgrade the power generation from 325MWe to 340MWe replaced the main water supply control valve in April 2013 began to adjust the main feed water control valve during the commissioning process, the valve in the manual operation state Under the overshoot and hysteresis, low power conditions, the flow fluctuations of 30T / H, can not be put into operation. In response to the above problems, the site organization and installation units, PAEC owners and Qinshan debugging team conducted a technical research, has studied a large number of historical data and technical information on the KMM control system and control valve technical information were studied, has taken the replacement of the valve pneumatic Amplifier, valve line sealing check, feedback lever loose check, replace the valve positioner, adjust the valve pneumatic amplifier (relay), adjust the valve positioner PID parameters, eliminate the valve stem friction and other methods were debugged, and ultimately Elimination of defects. In this paper, the main water supply control valve in the debugging process occurred in the phenomenon of failure, the measures taken and the effect were analyzed.