济宁市煤气公司现存在以下重大火险隐患:一、煤气柜院内是甲类重点防火要害部位,是严禁烟火的地方,但实际上烟火没禁,检查中发现地面上烟头到处可见。二、煤气柜距泵房、配电室20.5米,达不到《建筑设计防火规范》规定的防火间距不应少于35米的要求。三、泵房使用的防爆开关、防爆电机的引线接头部位气密性不好,没有防止可燃气体侵入的保护措施,达不到煤炸危险场所线路安装的防火要求。这些隐患的存在,严重威胁着储气站及周围单位的安全。
Jining City Gas Company there are hidden dangers of the following major fire hazards: First, the gas cabinet hospital is a key fire safety parts of the site is a non-smoking fireworks, but in fact the fireworks were banned, check found on the ground Cigarette can be seen everywhere. Second, the gas cabinet from the pump room, power distribution room 20.5 meters, less than “architectural design code for fire protection,” the provisions of the fire prevention spacing should not be less than 35 meters. Third, the pump room explosion-proof switch, explosion-proof motor lead connector parts gas tightness is not good, there is no protective measures to prevent the intrusion of combustible gases, reach the line of coal-fired dangerous place fire safety requirements. The existence of these hidden dangers seriously threatens the safety of the gas station and the surrounding units.