1995年9月13日我省某县电力承装公司在新建10kV线路施工接近尾声时,参加该工程施工的一位线路工,登上新线路(甲线)第~#31杆,搭接两耐张段之间的跳线时,右手触及导线触电,经抢救无效死亡。经查,发生触电的主要原因是该新线路(甲线)第~#11转角耐张杆的一处拉线盘埋深不足(设计要求1.7m;实际仅1m)再加上雨水冲刷,拉线松动,电杆倾斜(电杆为12m拔稍杆,要求埋深是1.9m,实际仅
On September 13, 1995, a county electric power loading company in our province approached the end of the construction of a new 10kV line and participated in the construction of a line worker who boarded the # 31 line of the new line (A line) and lapped two Jumper between segments of tension, the right hand touches the wire electric shock, died of rescue invalid. After investigation, the main cause of electric shock is the lack of depth of a cable tray (~ 1.7m in design; only 1m in actuality) at the ~ # 11 corner tension bar of the new circuit (A line) coupled with rainfall erosion and loosening of the cable , Pole tilt (pole for the 12m pull a little rod, requiring depth is 1.9m, the actual only