我们在平顶山高压开关厂的设计中采用了以150℃高温热水为热媒的辐射采暖系统,取供回水温差Δt=60℃。中间试验系统于1974年冬开始投入运行,经三个冬天运行,供水温度变化在145℃至160℃之间,供回水温差变化在60℃至75℃之间,经受了一百余次人为停电和突然停电的考验,证明该系统基本上达到了运行安全可靠、维护简便的要求。一、设计简介 1.原始数据全厂设计负荷:~700万千卡/小时。中间试验负荷:
In the design of the Pingdingshan High-voltage Switchgear Factory, we used a radiant heating system using high-temperature hot water at 150°C as the heating medium. The temperature difference between the supply and return water was Δt=60°C. The intermediate test system was put into operation in the winter of 1974. After three winter runs, the temperature of the water supply changed from 145°C to 160°C. The temperature difference between the supply water and the return water changed from 60°C to 75°C, and it took more than one hundred times. The tests of power outages and sudden power outages have proven that the system basically meets the requirements of safe and reliable operation and easy maintenance. I. Introduction to the design 1. Raw data The whole plant design load: ~7 million kcal/hour. Intermediate test load: