受交流电气化铁道影响的水泥杆通信线路感应纵电动势允许值的标准问题,是国內外长期讨论的问题。本文论述了感应纵电动势的定义、感应纵电动势与对地电压之间的关系及决定感应纵电动势允许值标准的因素,指出了以通过人体允许电流与从导线经人体、电杆到地的阻抗相乘即为纵电动势允许值这一概念存在的问题,提出了必须考虑感应纵电动势內阻的观点,并对通信线路在正常通话状态和接地故障状态下,感应纵电动势的內阻进行了分析与计算,得出了在接触网正常运行状态取60伏、接触网短路状态取430伏是安全可行的结论。
The standard issue of the allowable value of longitudinal electromotive force induced by the communication line of cement pole with the influence of AC electrified railway is a long-term discussion at home and abroad. This paper discusses the definition of the induced longitudinal electromotive force, the relationship between the induced longitudinal electromotive force and the ground voltage, and the factors that determine the allowable value of the induced longitudinal electromotive force. It is pointed out that the impedance of the current through the human body and the impedance Multiplication is the problem of the concept of longitudinal electromotive force. The viewpoint that the internal resistance of the induced longitudinal electromotive force must be considered, and the internal resistance of the longitudinal electromotive force induced by the communication line in the normal communication state and the ground fault state are analyzed With the calculation, it is concluded that it is safe and feasible to take 60 volts in the normal operation of catenary network and 430 volts in catenary short circuit condition.