摘要:随着信息基础设施建设步伐的加快,计算机信息机房的监测系统已作为现阶段机房建设的一个重要组成部分。浙江省新华医院计算机信息中心机房集中着大量的设备,需要建立一个先进的、完善的机房监测系统的操作管理平台, 对机房内的供配电、UPS、温湿度,漏水、精密空调、等实现集中监控、集中管理,同时也节约了大量的人力财力。提高无人值守机房和设备的安全性及便利性,达到了机房的科学管理。
关键词:计算机信息 机房监测系统
Abstract: Along with the information infrastructure construction step speeding up, the computer information system has been the engine room at this stage of the construction of the room as an important component. Zhejiang xinhua hospital center room with computer information on a lot of equipment, need to build an advanced and perfect computer room monitoring system operation management platform, of computer room of the power supply, UPS within, temperature, humidity, water, air conditioning, and realize the precise centralized monitoring, centralized management, and also save a lot of money and effort required. Improve the unattended engine room and the safety of the device and convenience to the computer science management.
Keywords: computer information, room, monitoring system
中圖分类号:TN931.3 文献标识码:A文章编号:
一、概述
随着信息基础设施建设步伐的加快,计算机信息机房的监测系统已作为现阶段机房建设的一个重要组成部分。机房的设备(供配电、 UPS、空调、消防、保安等)时刻关系着机房内计算机系统正常的运行与否,一旦机房环境设备出现故障,就会影响计算机系统运行,对其数据传输、存储及系统运行的可靠性构成威胁,如事故严重又不能及时处理,就可能损坏硬件设备,造成严重后果。
浙江省新华医院计算机信息中心机房集中着大量的设备,需要建立一个先进的、完善的机房监测系统的操作管理平台, 对机房内的供配电、UPS、温湿度,漏水、精密空调、等实现集中监控、集中管理,同时也节约了大量的人力财力。从而减轻了机房维护人员负担,提高劳动生产率,提高了维护质量和维护水平的可靠性,实时远程监控,提高无人值守机房和设备的安全性及便利性,达到了机房的科学管理。
二、监测系统设计说明
1、系统结构
浙江省新华医院的计算机机房监测系统包括以下子系统:
供配电监控系统
UPS后备电源监控系统
空调监控系统
漏水监测系统
温、湿度监测系统
消防监视系统
报警系统(多媒体语音、电话语音、短信报警)
监测系统实时显示并保存各监测参数的数值,设定参数的上限值与下限值,当监测的参数超过设定的允许值时,系统诊断为有故障(报警)事件发生,监控系统立刻弹出相应的报警页面窗口,支持多媒体声音报警、自动拨打预设电话、短消息等,实现报警,通知值班人员或相应的主管人员。系统支持可查询任一监测对象的历史记录(列表、曲线)。
2、供配电系统
1)、电源参数
监测对象:2台配电柜
在两台配电柜内各装一台电量仪,通过Cat 6四对非屏蔽双绞线将电量仪检测的信号(RS485)传输到检测主机上的智能控制器。需检测的每路电(三相或单相),在配电柜里分别要配相应的电流互感器(CT),用以检测各相电流值。系统实时显示并保存配电柜主输入的三相电及各支路的检测参数的数值;设定电压、电流的上限值与下限值。当系统检测的电压或电流超过设定的上限、下限值时,系统即诊断为有故障或报警事件发生,监控主系统立刻弹出相应的报警页面窗口,伴有多媒体语音报警和短信报警,通知值班人员或相应的主管人员;事后可查询任一检测对象的历史记录(列表、曲线)。
参考图例:
2)、开关状态
监测对象:主要触点
选用转换模块和开关量检测模块来实时检测配电柜内的主要回路的触点开闭状态。
3)、UPS监控
监测对象:2台UPS
实施方案:
通过UPS厂家提供的通讯协议进行二次开发,对现场监控室的2台UPS进行全面系统的监测与诊断。详细内容有:输入电压、旁路电压、负载电压、逆变器电压、输入电流、旁路电流、负载电流、逆变器电流、输入频率、旁路频率、负载频率、逆变器频率、功率因素、各相有功功率、标称功率、电池备份时间、负载量及UPS整流器、逆变器、电池的工作状态等(注:不同型号的UPS监视的参数会有所不同)。当UPS任意一个参数出现异常时以及 UPS任意部件出现故障信息时,监控主机会自动弹出UPS相关画面,在有发生异常的位置出现明显的颜色变化,并且同时会弹出报警界面,伴有多媒体语音报警和短信报警等,通知值班人员或相应的主管人员,并且事后可查询任一检测对象的历史记录(列表、曲线)。
参考图例:
3、空调系统
监测对象:1台精密空调
实施方案:
对于精密空调,系统通过对通信协议的二次开发实时监测精密空调内部的各模块压缩机、风机、加湿器、去湿器、加热器工作情况及设定温湿度、回风温湿度、控制状态(本机、远程、微机)和温湿度报警等。当空调出现故障信息时,监控主机会自动弹出空调相关画面,在有发生异常的位置出现明显的颜色变化,伴有多媒体语音报警和短信报警等,通知值班人员或相应的主管人员,事后可查询任一检测对象的历史记录(列表、曲线)。
参考图例:
4、监测报警系统
监测对象:1台精密空调的漏液情况
实施方案:
考虑到机房并没有其他水源,故只对1台恒温恒湿空调进行测漏监控。系统采用美国TraceTek带定位漏水测漏系统TTSIM 一套,感应线缆沿空调下面围绕一周,当感应线缆感应到某处有漏水事件发生时系统将即刻响应,弹出相应的报警窗口,并显示具体的漏液位置,还将通过多媒体声音报警并自动发短信、邮件、电话通知相关人员前来处理,并且事后可查询任一检测对象的历史记录(列表、曲线)。
参考图例:
5、温湿度系统
监测对象:机房区域的温湿度状态
实施方案:
选用一体化带液晶面板温湿度传感器对机房进行温湿度监测,系统可实时显示(电子地图方式)并记录每个温湿度传感器所检测到的室内温度与湿度的数值,显示短时间段内的变化情况曲线图以及设定每个温湿度传感器的温度与湿度的上限与下限值并可查询任一检测对象的历史记录(列表、曲线)。
当任意一个温湿度传感器检测到的数据超过设定的上限或下限时,系统立刻弹出相应的报警窗口,同时监控主机发出多媒体声音报警及自动拨打预设电话,实现电话语音报警,通知值班人员或相应的主管人员,事后可查询任一检测对象的历史记录(列表、曲线)。
参考图例:
6、消防系统
监测对象:机房区域的烟感状态
实施方案:
通过消防控制器提供的干接点信号,实时检测火警信号,当消防主机能针对不同的区域提供独立的干结点信号时,系统即可监视到每个区域是否有报警。在以上报警方式发生的同时,现场值班室还将通过多媒体声音报警并自动拨号通知相关人员前来处理并且事后可查询任一检测对象的历史记录(列表、曲线)。
参考图例:
7、报警系统
以上提到的集中检测的配电柜、UPS、精密空调、 漏水检测、温湿度等系统,设备通过采控模块采集数据,以RS485方式传输至主机,对现场的数据按预先的安排,有条不紊地进入软件系统。主机通过网卡与机场内部局域网相连,经过AGENT采集后的所有数据通过软件设定,可将其数据往网上发送。在局域网以太网上可多点实现远程监测,但每个点均需要安装一套Client远端操作软件。
三、小结
浙江省新华医院计算机机房的监测系统的建成投入运行以来,系统性能稳定、可靠,为计算机信息机房的安全运行发挥了重要作用。
注:文章内所有公式及图表请用PDF形式查看。
关键词:计算机信息 机房监测系统
Abstract: Along with the information infrastructure construction step speeding up, the computer information system has been the engine room at this stage of the construction of the room as an important component. Zhejiang xinhua hospital center room with computer information on a lot of equipment, need to build an advanced and perfect computer room monitoring system operation management platform, of computer room of the power supply, UPS within, temperature, humidity, water, air conditioning, and realize the precise centralized monitoring, centralized management, and also save a lot of money and effort required. Improve the unattended engine room and the safety of the device and convenience to the computer science management.
Keywords: computer information, room, monitoring system
中圖分类号:TN931.3 文献标识码:A文章编号:
一、概述
随着信息基础设施建设步伐的加快,计算机信息机房的监测系统已作为现阶段机房建设的一个重要组成部分。机房的设备(供配电、 UPS、空调、消防、保安等)时刻关系着机房内计算机系统正常的运行与否,一旦机房环境设备出现故障,就会影响计算机系统运行,对其数据传输、存储及系统运行的可靠性构成威胁,如事故严重又不能及时处理,就可能损坏硬件设备,造成严重后果。
浙江省新华医院计算机信息中心机房集中着大量的设备,需要建立一个先进的、完善的机房监测系统的操作管理平台, 对机房内的供配电、UPS、温湿度,漏水、精密空调、等实现集中监控、集中管理,同时也节约了大量的人力财力。从而减轻了机房维护人员负担,提高劳动生产率,提高了维护质量和维护水平的可靠性,实时远程监控,提高无人值守机房和设备的安全性及便利性,达到了机房的科学管理。
二、监测系统设计说明
1、系统结构
浙江省新华医院的计算机机房监测系统包括以下子系统:
供配电监控系统
UPS后备电源监控系统
空调监控系统
漏水监测系统
温、湿度监测系统
消防监视系统
报警系统(多媒体语音、电话语音、短信报警)
监测系统实时显示并保存各监测参数的数值,设定参数的上限值与下限值,当监测的参数超过设定的允许值时,系统诊断为有故障(报警)事件发生,监控系统立刻弹出相应的报警页面窗口,支持多媒体声音报警、自动拨打预设电话、短消息等,实现报警,通知值班人员或相应的主管人员。系统支持可查询任一监测对象的历史记录(列表、曲线)。
2、供配电系统
1)、电源参数
监测对象:2台配电柜
在两台配电柜内各装一台电量仪,通过Cat 6四对非屏蔽双绞线将电量仪检测的信号(RS485)传输到检测主机上的智能控制器。需检测的每路电(三相或单相),在配电柜里分别要配相应的电流互感器(CT),用以检测各相电流值。系统实时显示并保存配电柜主输入的三相电及各支路的检测参数的数值;设定电压、电流的上限值与下限值。当系统检测的电压或电流超过设定的上限、下限值时,系统即诊断为有故障或报警事件发生,监控主系统立刻弹出相应的报警页面窗口,伴有多媒体语音报警和短信报警,通知值班人员或相应的主管人员;事后可查询任一检测对象的历史记录(列表、曲线)。
参考图例:
2)、开关状态
监测对象:主要触点
选用转换模块和开关量检测模块来实时检测配电柜内的主要回路的触点开闭状态。
3)、UPS监控
监测对象:2台UPS
实施方案:
通过UPS厂家提供的通讯协议进行二次开发,对现场监控室的2台UPS进行全面系统的监测与诊断。详细内容有:输入电压、旁路电压、负载电压、逆变器电压、输入电流、旁路电流、负载电流、逆变器电流、输入频率、旁路频率、负载频率、逆变器频率、功率因素、各相有功功率、标称功率、电池备份时间、负载量及UPS整流器、逆变器、电池的工作状态等(注:不同型号的UPS监视的参数会有所不同)。当UPS任意一个参数出现异常时以及 UPS任意部件出现故障信息时,监控主机会自动弹出UPS相关画面,在有发生异常的位置出现明显的颜色变化,并且同时会弹出报警界面,伴有多媒体语音报警和短信报警等,通知值班人员或相应的主管人员,并且事后可查询任一检测对象的历史记录(列表、曲线)。
参考图例:
3、空调系统
监测对象:1台精密空调
实施方案:
对于精密空调,系统通过对通信协议的二次开发实时监测精密空调内部的各模块压缩机、风机、加湿器、去湿器、加热器工作情况及设定温湿度、回风温湿度、控制状态(本机、远程、微机)和温湿度报警等。当空调出现故障信息时,监控主机会自动弹出空调相关画面,在有发生异常的位置出现明显的颜色变化,伴有多媒体语音报警和短信报警等,通知值班人员或相应的主管人员,事后可查询任一检测对象的历史记录(列表、曲线)。
参考图例:
4、监测报警系统
监测对象:1台精密空调的漏液情况
实施方案:
考虑到机房并没有其他水源,故只对1台恒温恒湿空调进行测漏监控。系统采用美国TraceTek带定位漏水测漏系统TTSIM 一套,感应线缆沿空调下面围绕一周,当感应线缆感应到某处有漏水事件发生时系统将即刻响应,弹出相应的报警窗口,并显示具体的漏液位置,还将通过多媒体声音报警并自动发短信、邮件、电话通知相关人员前来处理,并且事后可查询任一检测对象的历史记录(列表、曲线)。
参考图例:
5、温湿度系统
监测对象:机房区域的温湿度状态
实施方案:
选用一体化带液晶面板温湿度传感器对机房进行温湿度监测,系统可实时显示(电子地图方式)并记录每个温湿度传感器所检测到的室内温度与湿度的数值,显示短时间段内的变化情况曲线图以及设定每个温湿度传感器的温度与湿度的上限与下限值并可查询任一检测对象的历史记录(列表、曲线)。
当任意一个温湿度传感器检测到的数据超过设定的上限或下限时,系统立刻弹出相应的报警窗口,同时监控主机发出多媒体声音报警及自动拨打预设电话,实现电话语音报警,通知值班人员或相应的主管人员,事后可查询任一检测对象的历史记录(列表、曲线)。
参考图例:
6、消防系统
监测对象:机房区域的烟感状态
实施方案:
通过消防控制器提供的干接点信号,实时检测火警信号,当消防主机能针对不同的区域提供独立的干结点信号时,系统即可监视到每个区域是否有报警。在以上报警方式发生的同时,现场值班室还将通过多媒体声音报警并自动拨号通知相关人员前来处理并且事后可查询任一检测对象的历史记录(列表、曲线)。
参考图例:
7、报警系统
以上提到的集中检测的配电柜、UPS、精密空调、 漏水检测、温湿度等系统,设备通过采控模块采集数据,以RS485方式传输至主机,对现场的数据按预先的安排,有条不紊地进入软件系统。主机通过网卡与机场内部局域网相连,经过AGENT采集后的所有数据通过软件设定,可将其数据往网上发送。在局域网以太网上可多点实现远程监测,但每个点均需要安装一套Client远端操作软件。
三、小结
浙江省新华医院计算机机房的监测系统的建成投入运行以来,系统性能稳定、可靠,为计算机信息机房的安全运行发挥了重要作用。
注:文章内所有公式及图表请用PDF形式查看。