论文部分内容阅读
随着国民经济的不断发展,高层民用建筑越来越多。多年来作为高层民用建筑采暖、空调的动力设备一直使用燃油、燃气锅炉。根据《高层民用建筑设计防火规范》GB50045—1995(以下简称《高规》第4.1.2条规定:“燃油、燃气的锅炉……宜设置在高层建筑外的专用房间内。……当上述设备受条件限制必须布置在高层建筑或裙房内时,其锅炉的总蒸发量不应超过6t/h,且单台锅炉蒸发量不应超过2 t/h”。目前
With the continuous development of the national economy, there are more and more high-rise civil buildings. For many years, fuel and gas boilers have been used as power equipment for heating and air conditioning in high-rise civil buildings. According to “High-rise Civil Building Design Fire Prevention Code” GB50045-1995 (hereinafter referred to as “High Regulation” Article 4.1.2 stipulates: "The fuel, gas boiler ... should be set in a special room outside the high-rise building. ... When the above equipment When the conditions must be placed in a high-rise building or podium, the total evaporation of the boiler should not exceed 6 t/h, and the evaporation of a single boiler should not exceed 2 t/h.