量热计法室内侧制冷量计算公式,未考虑测量中小冷量空调器制冷量时空气处理柜除湿造成的误差。为排除此误差对测试结果的影响,采用称重法分别测量量热计内、外室加湿水及被测机的凝结水。利用基于称重法设计的量热计测得5台被测机的2组数据并进行分析,结果表明,当空调器的额定制冷量低于测试室输入功率时,空气处理柜的除湿量会增大测量偏差,且随着空调器制冷量的降低偏差增大。并对室内侧制冷量计算公式进行修正,以提高计算精确度。
Calorimeter indoor cooling capacity calculation formula, did not consider the measurement of small and medium capacity air-conditioning cooling capacity when the air handling cabinet dehumidification error. In order to rule out the influence of this error on the test results, weighing method were used to measure the condensation water inside and outside the room humidifying water and the tested machine respectively. Two sets of data of five tested machines were measured by the calorimeter designed on the basis of the weighing method and analyzed. The results show that when the rated cooling capacity of the air conditioner is lower than the input power of the testing room, the dehumidification capacity of the air handling cabinet will be Increase the measurement bias, and with the air conditioner cooling capacity to reduce the deviation increases. And the indoor side of the cooling capacity calculation formula is amended to improve the calculation accuracy.