摘要:主要讨论了220kV线路保护RCS-931A、PSL-603GA和PSL-631C重合闸的配合。由装置间二次回路接线图入手,结合保护装置说明书,分析装置回路间传递的信息、特殊压板功能和重合闸充放电条件。同时总结了此类配合中的注意事项,为运行人员提供可靠的操作依据,优化运行操作,对事故后分析重合闸动作情况提供帮助。
关键字:重合闸;特殊压板;充放电
Abstract: this paper is mainly discussed 220 kV line protection RCS-931 A, PSL-603 GA and PSL-631 C reclose cooperate. The secondary circuit between the device of the wiring diagram, combined with the protection device, this paper analyzes the information transmission between circuit device, special linking piece function and reclose charge and discharge conditions. It also summarizes the matters of attention in such cooperation, as operation personnel to provide reliable basis for the operation, optimize operation, after the accident analysis reclose movement situation provide help.
Key word: reclose; Special linking piece; Charging and discharging
中图分类号:TM77 文献标示码:B文章编号:
0 前言
目前电网中220kV线路保护采用双重化配置,PSL-603GA + PSL-631C组成的第一套线路保护和RCS-931A(第二套线路保护)双套保护加 CZX-12R2 操作箱的保护配置使用频率较高。运行中使用断路器保护PSL-631C的重合闸功能,其它两套保护和其配合。双重化保护配置保证了线路的可靠运行,但是增加了二次回路的复杂性,尤其是保护装置间重合闸的配合接线。
文章[1-3]虽对220kV线路重合闸进行分析,但大都局限于重合闸的某一部分,如沟通三跳、RCS-900系列保护至重合闸压板等,缺少对重合闸配合系统的分析和研究。本文将从保护间重合闸的启动回路、重合闸的相互闭锁回路、以及此类配合中的注意事项三个方面进行阐述,借此使变电运行人员深入理解保护间重合闸的配合、进一步提高变电运行人员相关操作及事故判断的准确性。
1 重合闸启动
重合闸的启动有两种方式:分别为保护跳闸启动重合闸、断路器位置启动重合闸。前者主要解决线路故障保护动作跳闸,后者主要解决正常运行下开关偷跳。重合闸启动回路接线如图1所示:(接线端子号可能有所不同、回路基本一致)
图1 重合闸启动回路
(1)1ZJ合后继接点开入
1ZJ为断路器操作箱CZX-12R2装置KK合后闭合接点,通过端子n98开入PSL631C装置合后继输入端子15n6x8,作为位置启动重合闸的一个判别(可由保护控制字整定投退)。操作箱可以提供此端子时最好接入,如不提供也可不接。
(2)断路器位置接点开入
1TWJa、1TWJb、1TWJc为断路器操作箱CZX-12R2三相跳闸位置辅助接点,通过端子n100、n101、n102开入PSL631C装置三相位置启动重合闸端子15n4x1、15n4x2、15n4x3,作为位置启动重合闸的另一个判别,实现位置启动重合闸。
(3)保护动作接点开入
1CKJA2、1CKJB2、1CKJC2、1CKJQ4为PSL-603GA装置保护A、B、C相跳闸输出和保护三相跳闸输出接点;TJA-2、TJB-2、TJC-2为RCS-931A装置保护A、B、C相跳闸输出接点,上述均为瞬时动作瞬时返回接点(保护动作返回该接点也返回),两组接点中A、B、C相跳闸接点并联开入PSL631C保护启动重合闸输入端子15n6x1、15n6x2、15n6x3;PSL-603GA装置三相跳闸输出接点1CKJQ4单独开入PSL631C保护三相启动重合闸输入端子15n6x4,实现保护跳闸启动重合闸。
RCS-931A装置保护三跳输出接点TJABC-1不能通过压板9LP15(闭锁另一套保护重合闸压板)开入PSL631C重合闸保护三相启动输入端子,因此此处不接线。9LP15壓板具体功能将在第三节详细介绍。
(4)重合闸启动条件
220kV线路重合闸方式普遍采用单相重合闸,以单相重合闸为例结合重合闸逻辑图说明重合闸的启动条件,在第二节中重合闸的充放电条件也以单相重合闸为例说明。
2 重合闸的相互闭锁
装置间重合闸的闭锁可以分为四个部分:操作箱CZX-12R2第一套重合闸闭锁接点与PSL-631C;操作箱CZX-12R2第二套重合闸闭锁接点与RCS-931A;装置RCS-931A与装置PSL-631C;装置PSL-603GA与装置PSL-631C,具体闭锁信号开入开出回路如图2所示:(接线端子号可能有所不同、回路基本一致)
图2 重合闸闭锁回路
2.1 操作箱与RCS-931A和PSL-631C间闭锁
以操作箱第一套重合闸闭锁接点与保护PSL-631C为例说明(操作箱第二套闭锁重合闸接点与保护RCS-931A的闭锁接线与此相同)。21YJJ接点为压力继电器21YJJ的动断辅助触点,开入装置压力闭锁重合闸接点15n4x8。正常运行时21YJJ处在得电动作状态,当断路器气压,液压压力降至不允许重合闸时,压力继电器21YJJ返回,其动断触点闭锁重合闸。
21SHJ手动或遥控合闸动合触点、13TJR和23TJR永跳接点、2ZJ手跳放电接点四个接点并联开入装置PSL-631C沟通三跳闭锁重合闸接点15n4x4。在合闸到故障线路、母差保护动作或线路保护发出永跳命令、手动或遥控跳闸时接点闭合使重合闸放电同时沟通三跳。
2.2 PSL-631C与RCS-931A间闭锁
PSL-631C对RCS-931A的闭锁通过接点GTST2来实现。GTST1、GTST2为常闭接点,正常状态下断开;在下列情况下该接点闭合:
1.重合闸为三重方式或停用
2.重合闸CPU告警
3.重合闸充电未满(包括+24V量开入15n4x4接点,压力低闭锁重合闸)
4.重合闸装置失电
在满足上述情况下GTST1,GTST2沟通三跳接点闭合,GTST1和PSL603GA保护的BDJ接点串联后开入操作箱的永跳回路。GTST2则开入RCS-931A沟通三跳闭锁重合闸接点610,实现对装置RCS-931A重合闸闭锁,同时沟通三跳。
RCS-931A对PSL-631C的闭锁通过闭锁重合闸接点 BCJ-1开入PSL-631C沟通三跳闭锁重合闸接点15n4x4来实现。BCJ-1为常开接点,当保护动作跳闸同时满足设定的闭重条件时,BCJ-1常开接点闭合。
3 重合闸配合中的注意事项
3.1 PSL-631C保护沟通三跳压板15LP18
该压板和沟通三跳接点GTST2、PSL-603GA保护动作接点BDJ串联开入操作箱永跳回路,在线路故障不满足重合条件时,都能不选相三相跳闸。由于该压板所在回路开入操作箱跳闸回路,而不是“使重合闸放电”,也不同于RCS-931A保护沟通三跳压板9LP21,因此正常运行时该压板放上。
3.2 RCS-931A闭锁PSL631C重合闸压板9LP15
该压板功能实际由两部分组成的,一是向另一套保护提供保护动作信息;二是向另一套保护提供重合闸闭锁信息。由于该压板只使用了其“放电”功能,因此将其命名为“闭锁另一套保护重合闸”压板。但是当使用该压板的两个功能时,该压板不易命名为“至重合闸”、“闭锁另一套保护重合闸”等名称。
3.3 RCS-931A保护沟通三跳压板9LP21
RCS-931A保护沟通三跳压板一端接+24V电源,一端开入RCS-931A沟通三跳闭锁重合闸接点610。因此正常运行时该压板在取下位置,重合闸停用时放上。
3.4 PSL-631C和RCS-931A的重合闸切换把手
PSL-631C重合闸方式开关打在停用位置,在闭锁本装置重合闸的同时,使GTST2沟通三跳接点闭合。
RCS-931A重合闸方式开关打在停用位置,仅表明本装置的重合闸停用,保护仍是选相跳闸。要实现线路重合闸停用,即任何故障三跳且不重,则应有+24V电压量开入“闭重三跳”(610端子)。GTST2沟通三跳接点闭合使该接点有+24V电压量开入,此时放上压板9LP21只为可靠。
參考文献
[1] 郭 雷,苏延武,赵慧君.RCS系列220kV线路保护_至重合闸_压板功能解析[J].电力系统保护与控制,2010,38(5):137-138
[2] DL/T559-94,220 kV-500 kV电网继电保护装置运行整定规程[S].
[3] 路改强,刘敏. 浅析500 kV系统中3/2接线方式线路重合闸[J].电力系统保护与控制,2009,37(23):141-144.
[4] 王宏茹,甘红庆,郭剑黎,高月梅.一起开关偷跳重合闸不动作的分析和改进[J].电力系统保护与控制,2010,37(24):201-206
[5] 国家电力调度通信中心.电力系统继电保护规定汇编[M].二版. 北京:中国电力出版社,2001.
注:文章内所有公式及图表请以PDF形式查看。
关键字:重合闸;特殊压板;充放电
Abstract: this paper is mainly discussed 220 kV line protection RCS-931 A, PSL-603 GA and PSL-631 C reclose cooperate. The secondary circuit between the device of the wiring diagram, combined with the protection device, this paper analyzes the information transmission between circuit device, special linking piece function and reclose charge and discharge conditions. It also summarizes the matters of attention in such cooperation, as operation personnel to provide reliable basis for the operation, optimize operation, after the accident analysis reclose movement situation provide help.
Key word: reclose; Special linking piece; Charging and discharging
中图分类号:TM77 文献标示码:B文章编号:
0 前言
目前电网中220kV线路保护采用双重化配置,PSL-603GA + PSL-631C组成的第一套线路保护和RCS-931A(第二套线路保护)双套保护加 CZX-12R2 操作箱的保护配置使用频率较高。运行中使用断路器保护PSL-631C的重合闸功能,其它两套保护和其配合。双重化保护配置保证了线路的可靠运行,但是增加了二次回路的复杂性,尤其是保护装置间重合闸的配合接线。
文章[1-3]虽对220kV线路重合闸进行分析,但大都局限于重合闸的某一部分,如沟通三跳、RCS-900系列保护至重合闸压板等,缺少对重合闸配合系统的分析和研究。本文将从保护间重合闸的启动回路、重合闸的相互闭锁回路、以及此类配合中的注意事项三个方面进行阐述,借此使变电运行人员深入理解保护间重合闸的配合、进一步提高变电运行人员相关操作及事故判断的准确性。
1 重合闸启动
重合闸的启动有两种方式:分别为保护跳闸启动重合闸、断路器位置启动重合闸。前者主要解决线路故障保护动作跳闸,后者主要解决正常运行下开关偷跳。重合闸启动回路接线如图1所示:(接线端子号可能有所不同、回路基本一致)
图1 重合闸启动回路
(1)1ZJ合后继接点开入
1ZJ为断路器操作箱CZX-12R2装置KK合后闭合接点,通过端子n98开入PSL631C装置合后继输入端子15n6x8,作为位置启动重合闸的一个判别(可由保护控制字整定投退)。操作箱可以提供此端子时最好接入,如不提供也可不接。
(2)断路器位置接点开入
1TWJa、1TWJb、1TWJc为断路器操作箱CZX-12R2三相跳闸位置辅助接点,通过端子n100、n101、n102开入PSL631C装置三相位置启动重合闸端子15n4x1、15n4x2、15n4x3,作为位置启动重合闸的另一个判别,实现位置启动重合闸。
(3)保护动作接点开入
1CKJA2、1CKJB2、1CKJC2、1CKJQ4为PSL-603GA装置保护A、B、C相跳闸输出和保护三相跳闸输出接点;TJA-2、TJB-2、TJC-2为RCS-931A装置保护A、B、C相跳闸输出接点,上述均为瞬时动作瞬时返回接点(保护动作返回该接点也返回),两组接点中A、B、C相跳闸接点并联开入PSL631C保护启动重合闸输入端子15n6x1、15n6x2、15n6x3;PSL-603GA装置三相跳闸输出接点1CKJQ4单独开入PSL631C保护三相启动重合闸输入端子15n6x4,实现保护跳闸启动重合闸。
RCS-931A装置保护三跳输出接点TJABC-1不能通过压板9LP15(闭锁另一套保护重合闸压板)开入PSL631C重合闸保护三相启动输入端子,因此此处不接线。9LP15壓板具体功能将在第三节详细介绍。
(4)重合闸启动条件
220kV线路重合闸方式普遍采用单相重合闸,以单相重合闸为例结合重合闸逻辑图说明重合闸的启动条件,在第二节中重合闸的充放电条件也以单相重合闸为例说明。
2 重合闸的相互闭锁
装置间重合闸的闭锁可以分为四个部分:操作箱CZX-12R2第一套重合闸闭锁接点与PSL-631C;操作箱CZX-12R2第二套重合闸闭锁接点与RCS-931A;装置RCS-931A与装置PSL-631C;装置PSL-603GA与装置PSL-631C,具体闭锁信号开入开出回路如图2所示:(接线端子号可能有所不同、回路基本一致)
图2 重合闸闭锁回路
2.1 操作箱与RCS-931A和PSL-631C间闭锁
以操作箱第一套重合闸闭锁接点与保护PSL-631C为例说明(操作箱第二套闭锁重合闸接点与保护RCS-931A的闭锁接线与此相同)。21YJJ接点为压力继电器21YJJ的动断辅助触点,开入装置压力闭锁重合闸接点15n4x8。正常运行时21YJJ处在得电动作状态,当断路器气压,液压压力降至不允许重合闸时,压力继电器21YJJ返回,其动断触点闭锁重合闸。
21SHJ手动或遥控合闸动合触点、13TJR和23TJR永跳接点、2ZJ手跳放电接点四个接点并联开入装置PSL-631C沟通三跳闭锁重合闸接点15n4x4。在合闸到故障线路、母差保护动作或线路保护发出永跳命令、手动或遥控跳闸时接点闭合使重合闸放电同时沟通三跳。
2.2 PSL-631C与RCS-931A间闭锁
PSL-631C对RCS-931A的闭锁通过接点GTST2来实现。GTST1、GTST2为常闭接点,正常状态下断开;在下列情况下该接点闭合:
1.重合闸为三重方式或停用
2.重合闸CPU告警
3.重合闸充电未满(包括+24V量开入15n4x4接点,压力低闭锁重合闸)
4.重合闸装置失电
在满足上述情况下GTST1,GTST2沟通三跳接点闭合,GTST1和PSL603GA保护的BDJ接点串联后开入操作箱的永跳回路。GTST2则开入RCS-931A沟通三跳闭锁重合闸接点610,实现对装置RCS-931A重合闸闭锁,同时沟通三跳。
RCS-931A对PSL-631C的闭锁通过闭锁重合闸接点 BCJ-1开入PSL-631C沟通三跳闭锁重合闸接点15n4x4来实现。BCJ-1为常开接点,当保护动作跳闸同时满足设定的闭重条件时,BCJ-1常开接点闭合。
3 重合闸配合中的注意事项
3.1 PSL-631C保护沟通三跳压板15LP18
该压板和沟通三跳接点GTST2、PSL-603GA保护动作接点BDJ串联开入操作箱永跳回路,在线路故障不满足重合条件时,都能不选相三相跳闸。由于该压板所在回路开入操作箱跳闸回路,而不是“使重合闸放电”,也不同于RCS-931A保护沟通三跳压板9LP21,因此正常运行时该压板放上。
3.2 RCS-931A闭锁PSL631C重合闸压板9LP15
该压板功能实际由两部分组成的,一是向另一套保护提供保护动作信息;二是向另一套保护提供重合闸闭锁信息。由于该压板只使用了其“放电”功能,因此将其命名为“闭锁另一套保护重合闸”压板。但是当使用该压板的两个功能时,该压板不易命名为“至重合闸”、“闭锁另一套保护重合闸”等名称。
3.3 RCS-931A保护沟通三跳压板9LP21
RCS-931A保护沟通三跳压板一端接+24V电源,一端开入RCS-931A沟通三跳闭锁重合闸接点610。因此正常运行时该压板在取下位置,重合闸停用时放上。
3.4 PSL-631C和RCS-931A的重合闸切换把手
PSL-631C重合闸方式开关打在停用位置,在闭锁本装置重合闸的同时,使GTST2沟通三跳接点闭合。
RCS-931A重合闸方式开关打在停用位置,仅表明本装置的重合闸停用,保护仍是选相跳闸。要实现线路重合闸停用,即任何故障三跳且不重,则应有+24V电压量开入“闭重三跳”(610端子)。GTST2沟通三跳接点闭合使该接点有+24V电压量开入,此时放上压板9LP21只为可靠。
參考文献
[1] 郭 雷,苏延武,赵慧君.RCS系列220kV线路保护_至重合闸_压板功能解析[J].电力系统保护与控制,2010,38(5):137-138
[2] DL/T559-94,220 kV-500 kV电网继电保护装置运行整定规程[S].
[3] 路改强,刘敏. 浅析500 kV系统中3/2接线方式线路重合闸[J].电力系统保护与控制,2009,37(23):141-144.
[4] 王宏茹,甘红庆,郭剑黎,高月梅.一起开关偷跳重合闸不动作的分析和改进[J].电力系统保护与控制,2010,37(24):201-206
[5] 国家电力调度通信中心.电力系统继电保护规定汇编[M].二版. 北京:中国电力出版社,2001.