丽泽金融商务区D10综合楼是呈反对称布置的一对弱连接框剪结构双塔高层建筑,与门式钢架门厅组成建筑群。高塔99m,比较规则;低塔70m,带长悬挑桁架;裙房3层,有长悬挑板,门厅带悬挂走廊。设计过程中针对弱连接裙房双塔结构的布置原则、长悬挑结构的加强方式及防连续倒塌设计、门式钢架门厅的舒适度控制,进行了细致分析,对一些关键构件明确了加强措施。此外,弱连接双塔底盘的计算地震剪力明显小于双塔底层的地震剪力之和,为保证安全度,采用SRSS方法对双塔底盘地震剪力进行加强性调整;长悬挑结构导致部分楼层框架承担的剪力超过25%,规范调整方法不再适用,采取针对性调整方法;软件对带V形支撑斜杆楼层的抗剪承载力计算方法有误,薄弱层判断失真,采取针对性计算方法。
D10 financial complex Lizhe Financial District is an anti-symmetrical arrangement of a pair of weak link frame shear structure of the twin-tower high-rise buildings, and the gated hall composed of buildings. Tower 99m, more rules; low tower 70m, with long cantilevered truss; podium 3, with long cantilevered panels, hallway with hanging corridor. In the process of design, the principle of double-column structure of weak connection podium, the strengthening method of long cantilever structure, the prevention of continuous collapse design and the comfort control of portal steel frame hall were analyzed in detail, and the key components were strengthened clearly Measures. In addition, the calculated seismic shear force of the weakly connected twin-tower chassis is obviously less than the sum of the seismic shear forces of the twin towers. To ensure the safety, the SRSS method is used to adjust the seismic shear force of the twin-tower chassis strongly. The shear force of the floor frame is over 25%, and the normative adjustment method is no longer applicable. The method of targeted adjustment is adopted. The calculation method of the shear capacity of the inclined-bar floor with V-shaped support is incorrect and the judgment of the weak layer is distorted. Calculation method.