针对某办公楼出现的室内相对湿度过高、新风量不足、空气有异味等问题 ,分析了设计资料并进行现场调研 ,采取降低冷水机组供回水温度、调节风机盘管风速、适当关闭风机盘管台数、清洗过滤器等措施 ,基本解决了室内空气品质问题。探讨了该工程空调系统设计中不足之处和运行管理中应注意的问题
Aiming at the problems such as excessive indoor relative humidity, insufficient fresh air volume and air smell in an office building, the design data were analyzed and the site investigation was conducted. The temperature of cooling water supply and return water was adjusted, the fan coil speed was adjusted, Tube number, cleaning filters and other measures to basically solve the indoor air quality problems. This paper discusses the shortcomings in the design of air-conditioning system and the problems that should be paid attention to in operation and management