2007年和2008年夏季,武钢氧气公司G台60000 m~3/h空分设备配套的氧压机和氮压机均发生因气体出口温度高而联锁停机的故障,其主要原因是循环水系统中风机冷却塔的冷却效果欠佳。采取相应改造措施后,使空分设备保持安全、稳定运行。文章详细介绍了对风机冷却塔和氧压机级间冷却器冷却水管采取的改造方案。
In 2007 and the summer of 2008, oxygen compressor and nitrogen compressor equipped with G 60000 m ~ 3 / h air separation plant of Wuhan Iron and Steel Company, Wuhan Iron and Steel Company, both occurred due to the high gas outlet temperature and the interlock shutdown occurred mainly due to circulating water The cooling effect of the fan cooling tower in the system is not good. Take the appropriate transformation measures, the air separation plant to maintain safe and stable operation. The paper introduces in detail the reformation plan for cooling pipe of cooling tower of fan tower and oxygen compressor.