针对南水北调中线工程35kV专用线路输电距离远、负荷点多、供电可靠性高等特点,首次提出了线路保护与监控互补设计的理念。即利用监控系统的操作功能(故障判别、故障隔离及故障恢复等)弥补35kV专用输电线路保护缺陷(保护动作无选择性等)、利用光纤综保装置的采集功能节省35kV专用输电线路测控终端模块,并借助已建立的光纤通信网构造线路保护及数据通信双通道,以解决保护区与供电区分离的问题。
According to the characteristics of the 35kV special line of the middle route of South-to-North Water Diversion Project being characterized by long transmission distance, large load points and high reliability of power supply, the concept of complementary design of line protection and monitoring is proposed for the first time. That is to use the operation of the monitoring system functions (fault identification, fault isolation and fault recovery, etc.) to make up for 35kV dedicated transmission line protection defects (protection action without selectivity, etc.), the use of optical fiber comprehensive protection device acquisition saves 35kV dedicated transmission line monitoring and control terminal module , And with the established optical fiber communication network to construct dual-channel line protection and data communications in order to solve the separation of protected areas and power supply area.