对于设置高位消防水箱的临时高压消防给水系统,已作废规范《高层民用建筑设计防火规范》GB50045-95(2005)规定:增压水泵的出水量,对消火栓给水系统不应大于5L/S,对于自动喷水灭火系统不应大于1L/S;气压罐的调节水容量宜为450L。而《消防给水及消火栓系统技术规范》GB50974-2014(以下简称为《消规》)对于增压稳压设备的设置要求则有明显的不同。本文结合具体工程实例对增压稳压设备在实际工程中的应用计
For the installation of high-pressure fire water tank temporary high-pressure fire water supply system, has abandoned the Code “Fire Code for High-rise Civil Building Design” GB50045-95 (2005) provides that: booster pump water output, fire hydrant water supply system should not exceed 5L / S, Sprinkler system should not be greater than 1L / S; pressure tank to adjust the water capacity should be 450L. The “fire water and fire hydrant system technical specifications” GB50974-2014 (hereinafter referred to as “consumer regulatory”) for the booster regulator equipment setting requirements are significantly different. This article combined with specific engineering examples of booster regulator equipment in practical engineering applications