1992年6月初,位于我市中区××宾馆一台WNS2-8-Q型天然气锅炉在点火时突然发生炉膛爆炸,爆炸气浪掀开烟道处的防爆门,将烟囱出口增设的消声装置撕脱,抛出30多米远。由于是清晨,行人稀少,未造成伤亡。事故发生后,我们进行了现场调查,判断是吹扫不充分,炉膛内残存的可燃性气体与空气混合比在爆炸极限内,点火时发生爆炸事故。经检查点火程序保护装置工作正常(点火前期吹扫为十分钟,符合设计使用要求),天然气电磁阀有轻微泄漏。显然,燃气电磁阀的泄漏是不允许的,但根据泄漏程度分析以及模拟十分钟吹扫足以吹尽炉膛内的余气,导致这起吹
At the beginning of June 1992, a WNS2-8-Q natural gas boiler located in XX Hotel in Central City suddenly exploded in the hearth when it was ignited. The explosion blast opened the explosion-proof door at the flue and added the noise reduction at the outlet of the chimney Device avulsion, throwing more than 30 meters away. As it is early morning, pedestrians are sparsely populated, causing no casualties. After the accident, we conducted a field survey to determine the purging is not sufficient, the remaining combustible gas in the furnace and air mixture ratio within the explosion limit, the ignition explosion occurred. After checking the ignition program protection device is working properly (pre-ignition purge for ten minutes, in line with design and use requirements), natural gas solenoid valve has a slight leak. Obviously, gas solenoid valve leakage is not allowed, but according to the degree of leakage analysis and simulation of 10 minutes purge enough to blow off the remaining gas in the furnace, resulting in this blow