论文部分内容阅读
顶棚吊灯有时有轻微的抖动,甚至有幅度较大的摆动并伴有响声。这种现象一般是由吊顶内中央空调系统的风管或风机盘管的振动引起的。当空调系统开启后,风管内空气的流动及该系统传动部分偏心等造成振动并传递给了吊灯。为了避免这种现象的发生,同时也避免顶棚因此产生变形,施工过程中可采取以下预防措施。1.安装风管或风机盘管的吊杆时,绝对不与吊顶用的吊杆混用。2.风管或风机盘管连同吊具都不能与吊顶系统有任何连接或接触。当风管宽度过大时,为满足吊顶吊杆的间距要求,可采用型钢扁担的形式,从风管底
Ceiling chandeliers sometimes have a slight jitter, or even a larger swing and accompanied by a sound. This phenomenon is generally caused by the ceiling of the central air conditioning system duct or fan coil vibration caused. When the air-conditioning system is turned on, the air flow in the air duct and the partial transmission of the system cause vibration and are transmitted to the chandelier. In order to avoid this phenomenon, but also to avoid the ceiling deformation, the construction process can take the following precautions. 1. When installing the boom of the air duct or the fan coil, it should not be mixed with the boom used for the ceiling. 2. Duct or fan coil together with the spreader can not have any connection or contact with the ceiling system. When the duct width is too large, in order to meet the spacing requirements of suspended ceiling boom can be used in the form of steel pole, from the bottom of the duct