《农村低压电力技术规程》(DL499-92)2.8条规定:连接组别为Y,yno的配电变压器,三相负荷应尽量平衡,不得仅用一相或两相供电。中性线或保护中性线的电流不应超过低压侧额定电流的 25%. 2.17.4条规定:中性线不得装设熔断器或单独的开关装置。《?
Section 2.8 of Technical Specification for Rural Low-Voltage Electricity (DL499-92) states: For distribution transformer with connection group Y and yno, the three-phase load should be balanced as far as possible, and it is forbidden to use only one or two phase power supply. Neutral or neutral current should not exceed 25% of the rated current on the low side. 2.17.4 states: Neutral shall not be equipped with fuses or separate switching device. "?