文章计算了大朝山水电厂发电机在孤立运行、电压为额定值且不计励磁调节器作用的工况下 ,内部相间和匝间短路的最小稳态短路电流及相应的保护灵敏系数。分析表明 ,高灵敏单元件横差、不完全和完全纵差保护可以构成本发电机的双重或三重化主保护
The paper calculates the minimum steady-state short-circuit current and the corresponding protection sensitivity coefficient of the internal inter-phase and inter-turn short circuits when the generator of the Dachaoshan Hydropower Plant operates in isolation and the voltage is rated and ignores the action of the excitation regulator. Analysis shows that the high sensitivity of single-element differential, incomplete and fully differential protection can constitute the double or triple main protection of the generator