2014年冬季供暖期间,对首都机场T2航站楼室内主要功能区相关空调设计参数进行测试,记录并分析了温度、相对湿度和风速的测试结果。测试结果表明,冬季供暖期间,航站楼室内存在温度偏高、相对湿度偏低以及外围区域受冷风侵入严重等问题。此次测试参数分布特性可为航站楼内气流组织的优化设计及空调系统调节控制提供参考意见。同时,对高大空间建筑热环境和空调设计具有一定的指导意义。
During the winter heating in 2014, the design parameters related to the air conditioning in the main function areas of the terminal building of Capital Airport T2 were tested, and the test results of temperature, relative humidity and wind speed were recorded and analyzed. The test results show that there are some problems such as high temperature, low relative humidity and severe intrusion of cold wind in the terminal area during winter heating period. The distribution of the test parameters can provide reference for the optimal design of air flow in the terminal building and the control of the air conditioning system. At the same time, it has some guiding significance for the design of thermal environment and air conditioning in tall buildings.