近两年,我地发生多起变配电设备事故,其中有三起较为严重.1 情况和原因1.1 1997年元月,某水泥厂2×800 kV·A变压器低压侧平均电压在450 V以上,为了不影响生产生活,厂电工决定将变压器分接开关由Ⅲ档调至Ⅰ档,当其中一台调整完毕合闸送电后不到2分钟,瓦斯保护就动作跳闸.某电力施工队闻讯立即前往测试,变压器高、低压侧绕组直流电阻均正常,但未做耐压试验.当时认为是分接开关故障,打算购买分接开关予以更换.笔者了解到在测试直流电阻时分接开关旋转自如,瓦斯继电器内气体为淡黄色且可燃.分析认为系分接开关调整不到位.介乎Ⅰ、Ⅱ档之间,导致匝间短路绝缘破坏.吊芯检查证明如此.
In the past two years, there have been a number of power distribution equipment accidents in our country, of which three were more serious.1 Situation and Causes 1.1 In January 1997, the average voltage on the low-voltage side of a 2 × 800 kV A transformer in a cement plant was above 450 V, In order not to affect the production and life, the electrician decided to switch the transformer tap changer from the third gear to the first gear, and when less than 2 minutes after the completion of one of the adjustments, the gas protection was tripped. Immediately went to the test, the transformer high and low voltage side winding DC resistance are normal, but not to withstand voltage test was considered a tap changer, intended to buy tap changer to replace the author learned that the test DC resistance tap switch spin freely , Gas relay gas yellow and flammable.Analysis that the Department of the tap changer is not in place.Stage Ⅰ, Ⅱ between the file, resulting in inter-turn short circuit insulation damage.