近日笔者在值班时发现一起10kV线路故障.当时天气晴朗,10kV母线B相接地,同时一条出线过流跳闸,重合复跳,母线仍然接地.拉开另一出线接地现象消除.后来用户来站说,当时10kV终端杆一根拉线被电弧烧断,10kV C相瓷瓶有放电痕迹,变压器、线路无其它任何故障.后试送电,试送成功.笔者认为,当时B相接地,A相、C相对地电压升高为线电压,由于所在地为重污染区,瓷瓶污染严重,绝缘强度不够而引起放电,又因瓷瓶、架构、拉线连为
Recently I found a 10kV line fault on duty when the weather was fine, 10kV bus B phase ground, while an overcurrent trip outlet, coincident jump, the bus is still grounded.Open another outlet of the ground to eliminate the phenomenon. Said that at that time a 10kV terminal rod is drawn by an electric arc, 10kV C-phase porcelain bottle has a discharge trace, and the transformer and the line have no other faults.After the test, the test-transmission is successful.I believe that when phase B is grounded, phase A , C relative voltage increased to line voltage, due to the location for the heavily polluted area, porcelain bottle serious pollution, insufficient dielectric strength caused by the discharge, but also because of porcelain, architecture, cable connection as