我厂热处理车间用XWB-101型仪表作圆图自动平衡记录调节仪,在使用过程中,曾出现“跑温”现象:即仪表指针即将达到或刚超过给定值的区域内就不运行,而炉内温度仍然下降或上升。造成跑温的主要原因是:因仪表长期连续工作,接触滚子沿滑线电阻往返移动,使其表面磨损或沾污,产生接触不良。若出现“跑温”,可采用下述办法消除。首先卸下滑线电阻罩,用细软麂皮或软刷蘸少许酒精(不能用汽油)洗刷滑线电阻和接触滚子。然后用下述方法判断仪表是否接触良好:仪表接上电源,热电偶输入端接上毫伏信号发生器。
I plant heat treatment plant with XWB-101-type instrument for the chart automatically balance the recording regulator, the use of the process, there have been “running temperature” phenomenon: the instrument pointer is about to reach or just exceed the given value of the region will not run, While the temperature in the furnace still drops or rises. The main reason for running temperature is: due to long-term continuous instrument, contact roller reciprocating along the sliding resistance, so that its surface wear or contamination, resulting in poor contact. If there is “running temperature”, you can use the following methods to eliminate. First remove the slip resistance cover, use a soft suede or a soft brush dipped in a little alcohol (can not use gasoline) scrub resistance and contact roller. Then use the following method to determine whether the instrument is in good contact: the meter connected to the power supply, thermocouple input connected to the millivolt signal generator.